| Plan Review Notes For Permit 03120591 |
| Permit Number |
03120591 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-18 00:00:00 | 1) TACTILE SIGNAGE IS REQUIRED AT | | | STAIRWELL DOORS. | | | | | | 2) ALL SHAFTWAYS THAT ARE LARGE ENOUGH | | | FOR PERSONS TO FALL INTO MUST BE MARKED | | | "SHAFTWAY" WITH 6" HIGH LETTERS. | | | | | | 3) NO FIRE SPRINKLER PLANS PROVIDED | | | WITH DRAWINGS. | | | | | | 4) PLEASE INDICATE ON THE PLANS, THE | | | REQUIRED EMERGENCY LIGHTS WITHIN STAIRS | | | 1 & 2. | | | | | | 5) PLEASE PROVIDE MORE DETAILS FOR | | | NOTE # 4 ON PAGE A-6.1. | | | | | | 6) A KNOX-BOX WILL BE REQUIRED FOR | | | THE BUILDING. | | | | | | 7) ELEVATOR WARNING SIGNS ARE REQUIRED | | | FOR THE BUILDING AT EACH ELEVATOR | | | OPENING. | | | | | | 8) NO ELEVATION DRAWINGS PROVIDED WITH | | | PLANS. | | | | | | 9) WHY ARE THE JANITOR'S CLOSET AND | | | LAUNDRY ROOM DOORS NOT FIRE RATED. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|