| Plan Review Notes For Permit 03120591 |
| Permit Number |
03120591 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-23 00:00:00 | *************** UNSAT ************** | | | | | | PLEASE SEE COMMENTS FROM OTHER PLANS | | | REVIEWERS, AS THEY MAY HAVE AN AFFECT ON | | | ELECTRICAL PLANS. | | | | | | 1)NOTE: PLEASE SEE 210.52 FOR RECEPT | | | SPACING. SEE W/IN 6' OF EDGE OF WALL AND | | | 2' OF WALL. | | | | | | 2)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS. PLEASE SEE SOME MISSING. | | | APT 2-1, APT 2-2. | | | | | | 3)NOTE: PLEASE SEE 700.12E FOR CIRCUIT- | | | -ING OF EM/EXT LTS. | | | | | | NOTE # 2 NOT PERMITTED. | | | 4)NOTE: PLEASESHOWS SD'S AS REQUIRED | | | PER NFPA-8-1. | | | PLEASE ALSO SEE 210.12 FOR CIRCUITING | | | OF SD'S. PANEL SCHEDULE SHOWS SD'S W/ | | | KITCHEN LTS. | | | | | | 5)NOTE: PLEASE SEE 250.24 FOR PLACEMENT | | | OF EQUIPMENT GROUNDING CONDUCTOR. | | | NONE UNTIL AFTER THE FIRST MEANS OF | | | DISC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-9717 | | | [email protected] |
|