Plan Review Notes
Plan Review Notes For Permit 03120591
Permit Number 03120591
Review Stop B
Sequence Number 1
Notes
Date Text
2004-01-13 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 03120591
 ADD: 533 CLEMATIS STREET
 CONT: SHAKMAN CONSTRUCTION
 TEL: (561)239-9018
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST BUILDING REVIEW:
 ACTION: DENIED
 NOTE:
 3401.7.2.6 WHEN REPAIRS AND ALTERA-
 TIONS AMOUNTING TO MORE THAN 50% OF THE
 VALUE OF THE EXISTING BUILDING ARE MADE
 DURING ANY 12 MONTH PERIOD, THE BUILDING
 OR STRUCTURE SHALL BE MADE TO CONFORM TO
 THE REQUIREMENTS FOR A NEW BUILDING OR
 STRUCTURE OR BE ENTIRELY DEMOLISHED.
  
  
 1)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 A SURVEY OR PLOT PLAN INDIATING THE PROP
 ERTY LINES, AND THE DISTANCE AWAY FROM
 THE PROPERTY LINE?THE DISTANCE THE
 BUILDING STEPS BACK AT THE 2ND AND 3RD
 FLOORS? WINDOW SIZES VS WALL %/ FLOOR.
 705.1.1.2 EVERY EXTERIOR WALL WITHIN
 15' OF A PROPERTY LINE SHALL BE EQUIPPED
 WITH APPROVED OPENING PROTECTIVES.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 STAIR# 2, IS THIS A FIRE ESCAPE OR CON-
 SIDERED A EXTERIOR STAIR? A EXTERIOR
 STAIR SHALL COMPLY WITH 1006.2.4, WITH
 OPENING PROTECTIVES.
  
 3) STAIR# 2 EXIT DOOR ON THE 2ND & 3RD
 FLOORS, 1012.1.4 DURING ITS SWING, ANY
 DOOR IN A MEANS OF EGRESS SHALL LEAVE
 UNOBSTRUCTED AT LEAST 1/2 OF THE
 REQUIRED WIDTH OF LANDING.
  
 4) 903.8.1 BUILDINGS 3 STORIES OR MORE.
 ANY BUILDING 3 STORIES OR MORE IN HEIGHT
 SHALL BE EGUIPPED WITH AN APPROVED AUTO-
 MATIC SPRINKLER SYSTEMINSTALLED IN
 ACCORDANCE WITH 903.1. A STRAIGHT
 NFPA 13 SYSTEM WILL BE REQUIRED.
  
 5) EXISTING STAIRS, 1007.1.1(3) EXTERIOR
 AND INTERIOR EXIT STAIRWAYS SHALL BE CON
 STRUCTED OF NONCOMBUSTIBLE MATERIALS
 THROUGHOUT IN THE FOLLOWING BUILDINGS:
 (3) ALL OTHER BUILDINGS 3 STORIES OR
 MORE IN HEIGHT OR OCCUPIED BY MORE THAN
 40 PERSONS ABOVE OR BELOW THE LEVEL OF
 EXIT DISCHARGE.
  
 6) DISCREPANCY, SHEET A2.0 NOTE 11 INDI-
 CATES THAT THIS FLOOR WILL REMAIN A WOOD
 FLOOR SYSTEM VS S1,NOTE THIS AREA TO
 REMAIN "EXPOSED EARTH SLAB"?
  
 7) SHEET A-2.0 DEMO NOTES, INDICATE THE
 USE OF CALCULTED FLOOR ASSEMBLIES
 709.6.2.1, WHAT THE PLANS DO NOT INDI-
 CATE IS THE FASTENING SCHEDULE FOR THE
 3 LAYERS OF DRYWALL.
  
 8) DRAFTSTOPPING 2305.2.2(2) FLOOR/
 CEILING ASSEMBLIES,(2) MULTIFAMILY,
 TWO OR MORE UNITS R2, IN THE FLOOR/
 CEILING ASSEMBLIES ABOVE AND IN LINE
 WITH THE TENANT SEPAERATION, WHEN TENANT
 SEPERATION WALLS DO NOT EXTEND TO THE
 FLOOR SHEATHING ABOVE.
  
 9) SHEET S-2 INDICATES A DETAIL# 4, WOOD
 JOIST TO WALL CONNECTION, WHERE IS THIS
 USED? PLANS INDICATE THE REMOVAL OF
 THREE COURSES (FACE SHELL) HOW WILL THE
 REMAINDER OF THE WALL BE HELD IN PLACE?
  
 10) SHEET S-2 DETAIL# "CONNECTION A"
 THIS DETAIL INDICATES THE USE OF HILTI
 HIT SYSTEM, IS THIS TO GO INTO THE
 TERRA COTTA BLOCK, THE REMOVAL OF THE
 FACE SHELL IS DESIGNATED FOR THE OPPO-
 SITE SIDE OF THE WALL, ALSO HOW MANY
 COURSES ABOVE AND BELOW THIS SYSTEM?
  
 11) SHEET S-2 INDICATES HOW THE ELEVATOR
 PENTHOUSE IS TO BE BUILT, SIDEWALLS,
 PLYWOOD, TYPE V BUILDING SIDEWALLS ARE
 TO BE NONCOMBUSTIBLE.
  
 12) S-3 INDICATES THE LIVE LOADS FOR THE
 2ND & 3RD STORY AS 80 LBS FOR LIVE,
 STAIRS ARE TO BE 100 LBS/ SQ FT.
  
 13) STAIRWELL PROTECTION.
 SHEET M.2.1 3RD FLOOR STAIR WELL HAS A
 12"X12" RA RUNNING THROUGH THE STAIRWELL
 1006.1.3.1 PENETRATIONS INTO &
 THROUGH A STAIRWELL ENCLOSURE ASSEMBLY
 ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, DUCTWORK & EQUIPMENT FOR INDE-
 PENDENT STAIR PRESSURIZATION, SPRINKLER
 PIPING, STANDPIPES AND ELECTRICAL CON-
 DUIT SERVING THE STAIRWAY AND TERMINAT-
 ING AT A STEEL BOX NOT EXCEEDING 16 SQ
 INCHES.
  
 14)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS: FRONT ENTRY DOORS
  
 15) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 16)1503.4.2 OVERFLOW DRAINS SHALL BE
 THE SAME SIZE AS ROOF DRAINS, INSTALLED
 WITH THE INLET FLOW LINE LOCATED 2"
 ABOVE THE LOWEST POINT OF THE ROOF LINE.
 OVERFLOW SCUPPERS SHALL BE A MINIMUM OF
 4"IN HEIGTH AND SHALL BE PLACED IN WALLS
 OR PARARETS WITH THE INLET FLOW LINE
 NOT LESS THAN 2" ABOVE THE ROOF SURFACE.
  
 17) 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 18)1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
 MECH. 301.13 WIND RESISTANCE
 MECHANICAL EQUIPMENT, APPLIANCES AND SUP
 PORTS THAT ARE EXPOSED TO WIND SHALL BE
 DESIGNED AND INSTALLED TO RESIST THE
 WIND PRESSURES ON THE EQUIPMENT & THE
 SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE ACCOMP
 LISHED BY DESIGN OR BY APPLICATION OF
 SECTION 301.13.1.
  
 19) FAIR HOUSING ACCESSIBLE ROUTE 4.3
 SHOW AN ACCESSIBLE ROUTE FOR THE SITE.
 INDICATE THE HANDICAPPED PARKING, ACCESS
 ISLES, AND ROUTE TO THE ELEVATOR. ALSO
 PROVIDE INFORMATION FOR ROUTE FOR PUBLIC
 TRANSPORTATION.
 INDICATE ALL SIDEWALKS, RAMPS,
 STAIRS, AND CURB CUTS.4.4/ 4.5
  
 20) SHEET A2.5 WATER CLOSET GRAB BARS,
 THE DETAIL INDICATES A 24" SIDE GRAB BAR
 BUT FIG 604.5.1 INDICATES A MINIMUM OF
 42" PLUS 12" FROM THE BACK WALL.
  
 21) SHEET A-6.1 FIRST FLOOR FRONT ENTRY
 DOORS VS PROPERTY LINE NOT GIVEN.
 3203.1 DOORS SHALL NOT OPEN OR
 PROJECT UPON PUBLIC PROPERTY.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026