2004-02-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMIN. CODE
 FLORIDA STATUTES.
  
 COMMENTS FROM PREVIOUS REVIEWS HAVE NOT
 BEEN ADDRESSED: (12-22-03 & 1-24-04) -
 NUMBERS WILL BE THE SAME FOR CLAIRITY.
 2) CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE, FOR GREASE INTERCEPTOR RE-
 QUIREMENTS. WASTE ORD. #2938-96 - (561)
 837-4074.
 6) SHT 24 FLOOR DRAINS ARE NOT APPROVED
 FOR INDIRECT WASTE. FLOOR SINKS ARE RE-
 QUIRED PER SECTION 802.3
 7) ALL SHEETS - THE DATE THAT THE SIGNA-
 TURE AND SEAL IS AFFEIXE AS PROVIDED
 HEREIN SHALL BE ENTERED ON SAID PLANS
 IMMEDIATELY UNDER THE SIGNATURE OF THE
 PROFESSIONAL ENGINEER. 61G15-23.002(1)
 AND FS 471.025.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]