Plan Review Notes
Plan Review Notes For Permit 03120577
Permit Number 03120577
Review Stop P
Sequence Number 2
Notes
Date Text
2004-01-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMIN. CODE
 FLORIDA STATUTES
  
 COMMENTS FROM PREVIOUS REVIEW HAVE NOT
 BEEN ADDRESSED: (12-22-03) - NUMBERS
 WILL BE THE SAME FOR CLAIRITY.
 1) ROUTE PLANS TO THE DEPT. OF BUSINESS
 REGULATION HOTEL & RESTURANT DIVISION
 FOR REVIEW PRIOR TO RESUMBITTING TO THE
 CITY FOR REVIEW. (954) 958-5520. SECTION
 101.4.7 - (PLANS MUST BE STAMPED AND
 COPIES OF THE SPECIFICATION SHEETS ATT-
 ACHED TO PLANS).
 2) CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE, FOR GREASE INTERCEPTOR RE-
 QUIREMENTS. WASTE ORD #2938-96- (561)
 837-4074.
 5) SHT 08 SANT. RISER DIAGRAM DOES NOT
 MEET CODE REQUIREMENTS. A TRAP IS REQ-
 UIRED FOR THE MOP SINK AND BOTH FLOOR
 SINKS. 1002.1
 6) SHT 24 FLOOR DRAINS ARE NOT APPROVED
 FOR INDIRECT WASTE. FLOOR SINKS ARE RE-
 QUIRED PER SECTION 802.3
 7) ALL SHEETS - THE DATE THAT THE SIGNA-
 TURE AND SEAL IS AFFIXED AS PROVIDED
 HEREIN SHALL BE ENTERED ON SAID PLANS
 IMMEDIATELY UNDER THE SIGNATURE OF THE
 PROFESSIONAL ENGINEER. 61G15-23.002(1)
 AND FS 471.025.
 NEW COMMENT*******
 1B SEE ATTACHED SHEET CONCERNING FLORIDA
 STATUTE 533.80(2)(B).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]