Plan Review Notes
Plan Review Notes For Permit 03120577
Permit Number 03120577
Review Stop E
Sequence Number 2
Notes
Date Text
2004-01-15 00:00:00************ UNSAT *****************
  
 1)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING EM/EXT LTS.
  
 2)NOTE: PLEASE SEE 220.12A FOR MIN LOAD
 REQUIRED FOR SHOW WINDOW(S). PLEASE SEE
 THAT PANEL IS ONLY SHOWING ONE CIRCUIT.
 200VA PER LINEAR FT.
  
 3)NOTE: PLANS MENTION TO PLACE RECEPTS
 ABOVE CEILING FOR "PLUG-IN" SIGNAGE.
 RECEPTS ARE NOT PERMITTED TO BE ABOVE
 THE DROP CEILING. CORDS MUST BE VISABLE
 FOR ITS ENTIRE LENGTH. NEC 410
  
 4)NOTE: PLEASE SEE OCP SHOWN FOR AHU.
 SHOWS 60A OCP FOR 5KW HEAT. PLEASE
 VERIFY OCP, MIN IS 125% 424.3B AND MAX
 TYP IS 150%.
  
 5)NOTE: PLEASE SEE 210.8B3 FOR ALL
 RECEPTS IN KITCEHN AREA TO BE GFI.
 PANEL SCHEDULE DOES NOT INDICATE THIS.
  
 6)NOTE: PLEASE VERIFY THREE LOCATIONS
 FOR CIRCUIT A-17?
  
 7)NOTE: PLEASE ALSO SEE OCP FOR FOR CU
 SHOWN AT 60A'S.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]