| Plan Review Notes For Permit 03120577 |
| Permit Number |
03120577 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-01-15 00:00:00 | ************ UNSAT ***************** | | | | | | 1)NOTE: PLEASE SEE 700.12E FOR CIRCUIT- | | | -ING EM/EXT LTS. | | | | | | 2)NOTE: PLEASE SEE 220.12A FOR MIN LOAD | | | REQUIRED FOR SHOW WINDOW(S). PLEASE SEE | | | THAT PANEL IS ONLY SHOWING ONE CIRCUIT. | | | 200VA PER LINEAR FT. | | | | | | 3)NOTE: PLANS MENTION TO PLACE RECEPTS | | | ABOVE CEILING FOR "PLUG-IN" SIGNAGE. | | | RECEPTS ARE NOT PERMITTED TO BE ABOVE | | | THE DROP CEILING. CORDS MUST BE VISABLE | | | FOR ITS ENTIRE LENGTH. NEC 410 | | | | | | 4)NOTE: PLEASE SEE OCP SHOWN FOR AHU. | | | SHOWS 60A OCP FOR 5KW HEAT. PLEASE | | | VERIFY OCP, MIN IS 125% 424.3B AND MAX | | | TYP IS 150%. | | | | | | 5)NOTE: PLEASE SEE 210.8B3 FOR ALL | | | RECEPTS IN KITCEHN AREA TO BE GFI. | | | PANEL SCHEDULE DOES NOT INDICATE THIS. | | | | | | 6)NOTE: PLEASE VERIFY THREE LOCATIONS | | | FOR CIRCUIT A-17? | | | | | | 7)NOTE: PLEASE ALSO SEE OCP FOR FOR CU | | | SHOWN AT 60A'S. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|