| Date |
Text |
| 2003-12-22 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLA. ADMIN. CODE |
| | FLA. STATUTES |
| | |
| | 1) ROUTE PLANS TO THE DEPT. OF BUSINESS |
| | REGULATION HOTEL & RESTURANT DIVISION |
| | FOR REVIEW PRIOR TO RESUBMITTING TO THE |
| | CITY FOR REVIEW. (954) 958-5520 |
| | SECTION 101.4.7 |
| | 2) CONTACT RODNEY COMPO, ENVIRONMENTAL |
| | COMPLIANCE, INDUSTRIAL PRETREATMENT FOR |
| | GREASE INTECEPTOR REQUIREMENTS. WASTE |
| | ORD. 2938-96. (561) 837-4074 |
| | 3) SHT 04 EQUIPMENT LEGEND #15 NOT LOCA- |
| | TED ON FLOOR PLAN. PLEASE CLAIRFY. SEC. |
| | 104.2.1 |
| | 4) WATER FILTER SHALL COMPLY WITH NSF |
| | STANDARDS. SUBMIT MANUF. SPECIFICATION |
| | SHEET.SECTION 303.4 |
| | 5) SHT 08 SANT. RISER DIAGRAM DOES NOT |
| | MEET CODE REQUIREMENTS. A TRAP IS REQ- |
| | UIRED FOR THE MOP SINK AND BOTH FLOOR |
| | SINKS. 1002.1 |
| | 6) SHT 24 FLOOR SINKS ARE NOT APPROVED |
| | FOR INDIRECT WASTE. FLOOR SINKS ARE RE- |
| | QUIRED PER SECTION 802.3 |
| | 7) ALL SHEETS - THE DATE THAT THE SIGNA- |
| | TURE AND SEAL IS AFFIXED AS PROVIDED |
| | HEREIN SHALL BE ENTERED ON SAID PLANS |
| | IMMEDIATELY UNDER THE SIGNATURE OF THE |
| | PROFESSIONAL ENGINEER. 61G15-23.002(1) |
| | FS 471.025. |
| | 8) ALL SHEETS - ENGINEERS SHALL LEGIBLY |
| | INDICATE THEIR NAME, ADDRESS AND LICENSE |
| | NUMBER ON EACH SHEET. IF PRACTICING |
| | THROUGH A DULY AUTHORIZED ENGINEERING |
| | BUSINESS, THE NAME, ADDRESS, AND CERTIF- |
| | ICATE OF AUTHORIZATION NUMBER OF THE |
| | ENGINEERING BUSINESS IS REQUIRED ON EACH |
| | SHEET. 61G15-23.002(2) - FS 471.025 |
| | 9) SHT 04 SHOW CLEAR FLOOR SPACE AND |
| | TURNING AREA IN ACCESSIBLE TOILET ROOM. |
| | SECTION 11-4.22.3 |
| | 10) RPZ BACKFLOW REQUIRED ON WATER SERV- |
| | ICE. SECTION 608.13.2 |
| | 11) THERMAL EXPANSION CONTROL REQUIRED |
| | PER 607.3.2. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |