Plan Review Notes
Plan Review Notes For Permit 03120577
Permit Number 03120577
Review Stop P
Sequence Number 1
Notes
Date Text
2003-12-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLA. ADMIN. CODE
 FLA. STATUTES
  
 1) ROUTE PLANS TO THE DEPT. OF BUSINESS
 REGULATION HOTEL & RESTURANT DIVISION
 FOR REVIEW PRIOR TO RESUBMITTING TO THE
 CITY FOR REVIEW. (954) 958-5520
 SECTION 101.4.7
 2) CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE, INDUSTRIAL PRETREATMENT FOR
 GREASE INTECEPTOR REQUIREMENTS. WASTE
 ORD. 2938-96. (561) 837-4074
 3) SHT 04 EQUIPMENT LEGEND #15 NOT LOCA-
 TED ON FLOOR PLAN. PLEASE CLAIRFY. SEC.
 104.2.1
 4) WATER FILTER SHALL COMPLY WITH NSF
 STANDARDS. SUBMIT MANUF. SPECIFICATION
 SHEET.SECTION 303.4
 5) SHT 08 SANT. RISER DIAGRAM DOES NOT
 MEET CODE REQUIREMENTS. A TRAP IS REQ-
 UIRED FOR THE MOP SINK AND BOTH FLOOR
 SINKS. 1002.1
 6) SHT 24 FLOOR SINKS ARE NOT APPROVED
 FOR INDIRECT WASTE. FLOOR SINKS ARE RE-
 QUIRED PER SECTION 802.3
 7) ALL SHEETS - THE DATE THAT THE SIGNA-
 TURE AND SEAL IS AFFIXED AS PROVIDED
 HEREIN SHALL BE ENTERED ON SAID PLANS
 IMMEDIATELY UNDER THE SIGNATURE OF THE
 PROFESSIONAL ENGINEER. 61G15-23.002(1)
 FS 471.025.
 8) ALL SHEETS - ENGINEERS SHALL LEGIBLY
 INDICATE THEIR NAME, ADDRESS AND LICENSE
 NUMBER ON EACH SHEET. IF PRACTICING
 THROUGH A DULY AUTHORIZED ENGINEERING
 BUSINESS, THE NAME, ADDRESS, AND CERTIF-
 ICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS IS REQUIRED ON EACH
 SHEET. 61G15-23.002(2) - FS 471.025
 9) SHT 04 SHOW CLEAR FLOOR SPACE AND
 TURNING AREA IN ACCESSIBLE TOILET ROOM.
 SECTION 11-4.22.3
 10) RPZ BACKFLOW REQUIRED ON WATER SERV-
 ICE. SECTION 608.13.2
 11) THERMAL EXPANSION CONTROL REQUIRED
 PER 607.3.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]