| Plan Review Notes For Permit 03120577 |
| Permit Number |
03120577 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-29 00:00:00 | NO MECHANICAL PLANS SUBMITTED FOR REIVEW | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | WITH MECHANICAL PERMIT APPLICATION. | | | 1.OUTSIDE AIR CALCULATIONS PER 2001 | | | FBC(M) 403.3. | | | | | | 2.EQUIPMENT SCHEDULE - INDICATE | | | LOCATION OF CONDENSER UNITS SHOULD A | | | SPLIT SYSTEM BE INSTALLED. | | | | | | 3.PROVIDE MANUFACTURER SUBMITTAL DATA | | | FOR THE FREEZER/REFRIGERATOR & DELI | | | COOLER. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|