| Plan Review Notes For Permit 03120577 |
| Permit Number |
03120577 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-23 00:00:00 | *************** UNSAT ************* | | | | | | 1)NOTE: PLANS ARE REQ'D TO BE SIGNED, | | | DATED AND SEALED BY THE ENGINEER OF | | | RECORD. 471.025 | | | PLEASE ALSO SEE THAT ALL SHEETS MUST | | | CONTAIN A TITLE BLOCK AS SET FORTH UNDER | | | FS 471 AND FAC 61G15-23.002 | | | PLEASE PROVIDE ALL LICENSE # 'S AS REQ'D | | | UNDER THE ABOVE REFERENCED FS'S/FAC'S | | | ALL SHEETS/ BOTH SETS. | | | | | | 2)NOTE: PLEASE PROVIDE ALL CIRCUITING | | | ON PLANS AND CORRELATE W/ SUBMITTED | | | PANEL SCHEDULE(S). | | | PLEASE ALSO SUBMIT SIZE OF EXISTING | | | SERVICE AND LOAD CALCULATIONS. 215.5 | | | PLEASE SHOW ALL LOAD CALCS PER 220 | | | PLEASE ALSO SEE 700.12E | | | | | | 3)NOTE: PLEASE SEE 210.62 FOR SHOW | | | WINDOW RECEPT REQUIREMENTS. DIRECTLY | | | ABOVE WINDOW. | | | | | | 4)NOTE: PLEASE SEE 600.5A FOR SIGN | | | CIRCUIT REQUIRED AT ENTRANCE. | | | | | | DUE TO PLANS NOT BEING COMPLETE AT THIS | | | TIME, THERE MAY BE OTHER COMMENTS TO | | | FOLLOW. | | | | | | PLEASE SEE ADMIN CODE 104 FOR CHANGE IN | | | USE AND POSSIBLE WORK THAT MAY BE REQ'D | | | TO BRING SPACE UP TO CODE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|