| 2004-01-13 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03120577 |
| | ADD: 107 N OLIVE AVE |
| | CONT: LWP CONSTRUCTION SERVICES INC |
| | TEL: (321)436-9394 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLANS, SPECIFICATIONS,REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | |
| | 2)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | SHEET# 08 INDICATES A RAISED WATER HEAT- |
| | ER PLATFORM, NO DETAIL FOR INSTALATION, |
| | DETAILS TO BE APPROVED BY ENGINEER OF |
| | RECORD. |
| | |
| | 3)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | SHEET#09 FRAMING NOTES (1) PREPARATION |
| | AREA DETAILS FOR SPECIFICATIONS ON THE |
| | FRAMING NEEDEDFOR THE VALENCE AND MENU |
| | BOARD, SHEET# 17 HAS NO ADDITIONAL INFO. |
| | |
| | 4)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | SHEET# 02 GENERAL NOTE# 20, PLANS DO NOT |
| | INDICATE IF THE RESTROOM IS TO BE RENO- |
| | VATED, NOR DOES THE RESTROOM INDICATE A |
| | 5'-0" TURNING RADIUS. WIDTH OF RESTROOM |
| | DOOR? |
| | |
| | 5) 11-4.1.6(2) DUTY TO PROVIDE ACCESS- |
| | IBLE FEATURES IN THE EVENT OF DISPROPOR- |
| | TIONALITY. INDICATE COMPLIANCE. |
| | |
| | 6)1204.2 SURROUNDING MATERIALS; |
| | THE WALLS & FLOORS OF ALL PUBLIC REST- |
| | ROOMS SHALL BE LINED WITH NONABSORBANT |
| | MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE |
| | FLOOR. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |