2004-01-13 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03120577
 ADD: 107 N OLIVE AVE
 CONT: LWP CONSTRUCTION SERVICES INC
 TEL: (321)436-9394
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET# 08 INDICATES A RAISED WATER HEAT-
 ER PLATFORM, NO DETAIL FOR INSTALATION,
 DETAILS TO BE APPROVED BY ENGINEER OF
 RECORD.
  
 3)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET#09 FRAMING NOTES (1) PREPARATION
 AREA DETAILS FOR SPECIFICATIONS ON THE
 FRAMING NEEDEDFOR THE VALENCE AND MENU
 BOARD, SHEET# 17 HAS NO ADDITIONAL INFO.
  
 4)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET# 02 GENERAL NOTE# 20, PLANS DO NOT
 INDICATE IF THE RESTROOM IS TO BE RENO-
 VATED, NOR DOES THE RESTROOM INDICATE A
 5'-0" TURNING RADIUS. WIDTH OF RESTROOM
 DOOR?
  
 5) 11-4.1.6(2) DUTY TO PROVIDE ACCESS-
 IBLE FEATURES IN THE EVENT OF DISPROPOR-
 TIONALITY. INDICATE COMPLIANCE.
  
 6)1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026