2003-12-16 00:00:00PROVISO:
 PLANS DO NOT INDICATE THE FIRE RATING OF
 THE WALL.SHOULD WALL CARRY A FIRE
 RATING, PROVIDE FIRE DAMPERS IN
 ACCORDANCE WTIH 2001 FBC(M) 607.1.2,
  
 TRANSFER GRILLE SHALL COMPLY WITH
 REVISION TO THE 2001 FBC(M) 601.4
 EFFECTIVE JUNE 30, 2003:
 RETURN SHALL USE 50 SQ INCHES OF GRILLE
 AREA TO 100 CFM OF SUPPLY AIR.
  