2006-01-25 00:00:00**********UNSAT *********
  
 1)NOTE: PLEASE SEE ADDRESSING NEEDS TO
 BE CORRECTED AS OUR SYSTEM IS SHOWING
 414 MADDOCK, THE PLANS IN FILE INDICATE
 414 ALSO, HOWEVER LTR IN FILE MENTIONS
 410 AND REV COVER SHEET INDICATES 408.
 PLEASE KNOW, ALL PLANS ON FILE CONTAIN
 414 IN THE TITLE BLOCK WHERE FAC
 61G15-23.002, 61G1-16.004 REQUIRES THE
 CORRECT ADDRESS FOR PROJECT TO BE ON THE
 TITLE BLOCKS FOR JOB.
  
 2)NOTE: PLEASE SEE RISER DIAGRAM
 INDICATES THE INSIDE PANEL (GARAGE)
 BEING FED BACK THROUGH THE METER CAN
 SHOWING LINE AND LOAD IN THE METER.
 PLEASE SEE THIS IS NOT PERMITTED.250.6
 ETC .
  
 3)NOTE: PLEASE SEE SERVICE IS SHOWING A
 MCB PANEL LOCATED OUTSIDE , HOWEVER IT
 IS HAS COME TO THE ATTENTION OF THIS
 OFFICE THAT THERE IS NO PANEL LOCATED
 OUTSIDE , AND ONLY A MAIN DISCONNECT?
 PLEAS CONFIRM AND REVISE ACCORDINGLY.
  
 4)NOTE: PLEASE PROVIDE REVISED PANEL
 SCHEDULE AS, SERVICE IS NOW SHOWN BEING
 DOWNGRADED TO 150A'[S WHEN ORIG PLANS
 CALLED FOR 200A'S, PLEASE PROVIDE ANY
 UPDATED CHANGES IN LOADS OR CIRCUITING.
 215.5
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  