| 2006-01-25 00:00:00 | **********UNSAT ********* |
| | |
| | 1)NOTE: PLEASE SEE ADDRESSING NEEDS TO |
| | BE CORRECTED AS OUR SYSTEM IS SHOWING |
| | 414 MADDOCK, THE PLANS IN FILE INDICATE |
| | 414 ALSO, HOWEVER LTR IN FILE MENTIONS |
| | 410 AND REV COVER SHEET INDICATES 408. |
| | PLEASE KNOW, ALL PLANS ON FILE CONTAIN |
| | 414 IN THE TITLE BLOCK WHERE FAC |
| | 61G15-23.002, 61G1-16.004 REQUIRES THE |
| | CORRECT ADDRESS FOR PROJECT TO BE ON THE |
| | TITLE BLOCKS FOR JOB. |
| | |
| | 2)NOTE: PLEASE SEE RISER DIAGRAM |
| | INDICATES THE INSIDE PANEL (GARAGE) |
| | BEING FED BACK THROUGH THE METER CAN |
| | SHOWING LINE AND LOAD IN THE METER. |
| | PLEASE SEE THIS IS NOT PERMITTED.250.6 |
| | ETC . |
| | |
| | 3)NOTE: PLEASE SEE SERVICE IS SHOWING A |
| | MCB PANEL LOCATED OUTSIDE , HOWEVER IT |
| | IS HAS COME TO THE ATTENTION OF THIS |
| | OFFICE THAT THERE IS NO PANEL LOCATED |
| | OUTSIDE , AND ONLY A MAIN DISCONNECT? |
| | PLEAS CONFIRM AND REVISE ACCORDINGLY. |
| | |
| | 4)NOTE: PLEASE PROVIDE REVISED PANEL |
| | SCHEDULE AS, SERVICE IS NOW SHOWN BEING |
| | DOWNGRADED TO 150A'[S WHEN ORIG PLANS |
| | CALLED FOR 200A'S, PLEASE PROVIDE ANY |
| | UPDATED CHANGES IN LOADS OR CIRCUITING. |
| | 215.5 |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW AND IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |