| 2003-12-23 00:00:00 | *************** UNSAT ************ |
| | |
| | 1)NOTE: PLEASE PROVIDE AIC RATING FOR |
| | MAIN/ PANEL. 110.9 MAINS/PANELS/BRKRS |
| | ARE ALL TO BE RATED FOR THE AVAILABLE |
| | FAULT CURRENT. |
| | |
| | 2)NOTE: PLEASE SEE NOTES ABOVE RISER |
| | DIAGRAM. PLEASE SEE NEC 680.22A5 FOR |
| | GFI'S AROUND POOL AREA. 20' NOT 15' |
| | PLEASE ALSO SEE 210.8A6 FOR GFI PROTECT- |
| | ION FOR RECEPTS SERVING KITCHEN COUNTER- |
| | SPACE IN KITCHENS. 6' RULE CHANGED |
| | |
| | 3)NOTE: PLEASE SEE THAT A GARAGE DOOR |
| | OPENER CIRCUIT ON PANEL SCHEDULE AND |
| | LOAD, HOWEVER PLANS DO NOT SHOW/INDICATE |
| | THIS RECEPT IN GARAGE. |
| | |
| | 4)NOTE: PLEASE SEE 210.52 FOR MISSING |
| | RECEPT IN BEDROOM? |
| | |
| | 5)NOTE: PLEASE PROVIDE ROOM DESIGNATION |
| | ON PLANS. |
| | |
| | 6)NOTE: PLEASE SEE 210.52C3 FOR MISSING |
| | RECEPT AT PENINSULAR. |
| | |
| | 7)NOTE: PLEASE LIST THE REQUIRED ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE PER 210.12. PLEASE ALSO SEE |
| | THE 2002 NEC AS THIS HAS CHANGED FROM |
| | THE 1999 NEC |
| | |
| | 8)NOTE: THIS IS ONLY A NOTE: PLEASE SEE |
| | THAT "PHONE" IS ONLY SHOWN IN KITCHEN |
| | AND ONE BEDROOM. PLEASE SHOW ALL |
| | LOCATIONS OF LV AT THIS TIME. IF NOT |
| | THNE REVISED PLANS WOULD HAVE TO BE |
| | SUBMITTED AT A LATER DATE. THIS IS JUST |
| | A NOTE; SPEAKER WIRING ETC. |
| | |
| | 9)NOTE: PLEASE SEE BOTH SMALL BEDROOMS |
| | SHOW A J-BOX IN CEILING W/ NO MEANS |
| | OF CONTROL? THIS IS ALSO JUST A NOTE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |