Plan Review Notes
Plan Review Notes For Permit 03120536
Permit Number 03120536
Review Stop B
Sequence Number 1
Notes
Date Text
2004-01-14 00:00:00DENIED
  
 1) PROVIDE COPY OF PAPERWORK FOR LOT
 SUBDIVISION APPROVED BY CITY ZONING
 DEPARTMENT AND NEW PCN FROM PALM BEACH
 COUNTY.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 4) REVISE THE TYPE OF CONSTRUCTION FROM
 TYPE V TO TYPE VI. BASED ON FBC TABLE
 600, THE PERCENT OF WALL ALLOWED AS
 OPENINGS IS EXCEEDED AND THE EXTERIOR
 WALLS WOULD HAVE TO HAVE A 2 HOUR FIRE
 RATING IF IT TYPE V UNPROTECTED
 CONSTRUCTION.
  
 5) THE MAXIMUM PRESSURES FOR OPENINGS
 LISTED ON SHEET 1 ARE INCORRECT. SEE FBC
 TABLE 1606.2B, WALL ZONE 5, 140MPH WIND
 SPEED AND 10 SQFT EFFECTIVE WIND AREA.
 FOR GARAGE DOOR SEE FBC TABLE 1606.2E
 FOR A 9'X7' DOOR AND ROOF ANGLE GREATER
 THAN 10 DEGREES.
  
 6) DETAIL 10 ON SHEET 3 FOR THE TIE BEAM
 DETAIL SPECIFIES ONE #5 TOP AND BOTTOM,
 BUT THE DRAWING SHOWS 2. PLEASE CORRECT.
  
 7) SPECIFY THE SPACING OF THE WEDGE
 ANCHORS FOR THE GARAGE DOOR BUCKS IN THE
 DETAIL ON SHEET 5. THE DIAMETERS OF THE
 WEDGE ANCHORS ARE GIVEN AS 1/2" AND 3/8"
 PLEASE INDICATE WHICH ONE IS CORRECT.
  
 8) PROVIDE A BUCK DETAIL FOR THE SIDE
 SWING DOORS.
  
 9) STRUCTURAL NOTE #11 ON SHEET 5 CALLS
 FOR THE ROOF SHEATHING TO BE NAILED WITH
 10D NAILS WHICH CONFLICTS WITH THE OTHER
 NOTES REQUIRING 8D NAILS. PLEASE CORRECT
  
 10) THE OWNER/AGENT IS REQUIRED TO SIGN
 AND DATE THE ENERGY CALC. FORM.
  
 11) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 SUBMIT FOR ALL WINDOWS, DOORS, ROOFING,
 STORM PANELS AND TRUSS CONNECTORS.
  
 12) SUBMIT THE DRAWINGS FOR THE SINGLE
 HUNG WINDOWS WHICH ARE MISSING FROM THE
 PRODUCT APPROVAL.
  
 13) SUBMIT PRODUCT APPROVALS FOR THE
 SINGLE OUTSWING DOORS AND DOUBLE
 OUTSWING GLAZED FRENCH DOORS.
  
 14) SUBMIT A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. INDICATE
 THE TYPE OF MOUNT, TYPE OF ANCHORS AND
 ANCHOR SPACING. THIS INFORMATION IS
 REQUIRED AT TIME OF APPLICATION OR A
 SEPARATE PERMIT AND FEE WILL BE REQUIRED
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved