| Plan Review Notes For Permit 03120529 |
| Permit Number |
03120529 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-24 00:00:00 | 1) WRONG FIRE CODE INFORMATION IN CODE | | | ANALYSIS BOX. SHOULD READ THE FLORIDA | | | FIRE PREVENTION CODE, 2000 EDITION, NOT | | | NFPA 101, 1985 EDITION. | | | | | | 2) THE FOUR CONSTRUCTION TRAILERS ARE | | | NOT TO INTERFERE WITH ANY FIRE LANES | | | OR FIRE HYDRANTS. | | | | | | 3) DEMOLITION, RENOVATION, AND | | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | | | 4) FIRE SPRINKLER HEADS ARE NOT TO BE | | | PAINTED WHEN THE ENTIRE CEILING DECK | | | IS PAINTED, THEY ARE TO BE REMOVED | | | AND REPLACED. | | | | | | 5) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | | | 6) ONLY ONE EMERGENCY LIGHT SHOWN IN | | | RECEIVING AREA. IS THIS ADEQUATE. | | | | | | 7) PLEASE INDICATE ANY EXISTING OR NEW | | | FIRE ALARM EQUIPMENT. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|