Plan Review Notes
Plan Review Notes For Permit 03120529
Permit Number 03120529
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-12-24 00:00:001) WRONG FIRE CODE INFORMATION IN CODE
 ANALYSIS BOX. SHOULD READ THE FLORIDA
 FIRE PREVENTION CODE, 2000 EDITION, NOT
 NFPA 101, 1985 EDITION.
  
 2) THE FOUR CONSTRUCTION TRAILERS ARE
 NOT TO INTERFERE WITH ANY FIRE LANES
 OR FIRE HYDRANTS.
  
 3) DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 4) FIRE SPRINKLER HEADS ARE NOT TO BE
 PAINTED WHEN THE ENTIRE CEILING DECK
 IS PAINTED, THEY ARE TO BE REMOVED
 AND REPLACED.
  
 5) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 6) ONLY ONE EMERGENCY LIGHT SHOWN IN
 RECEIVING AREA. IS THIS ADEQUATE.
  
 7) PLEASE INDICATE ANY EXISTING OR NEW
 FIRE ALARM EQUIPMENT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910