Plan Review Notes For Permit 03120501
Permit Number 03120501
Review Stop E
Sequence Number 2
Notes
Date Text
2004-01-15 00:00:00************ PROVSIO/ REVISION *******
  
 1)NOTE: PLEASE SHOW ALL NEW CIRCUITING
 ON PLANS AND CORRELATE WITH A PANEL
 SCHEDULE TO BE SUBMITTED.
  
 2)NOTE: PLEASE ALSO INCLUDE WHAT APPEARS
 TO BE A NEW A/C SYSTEM . PLEASE VERIFY
 NEW OR EXISTING ROOF TOP RECEPT.
 IF NEW A/C SYSTEM, PLEASE ALSO SUBMIT
 LOAD CALCULATIONS ON PANELS.
  
 3)NOTE: PLEASE SHOW ALL CIRCUITING FOR
 EM/ EXT LTS PER 700.12E.
  
 PLEASE SUBMIT ALL OF THE ABOVE INFORMAT-
 -ION FOR REVIEW BEFORE ANY ROUGH
 ELECTRICAL INSPECTION IS CALLED IN.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW