Plan Review Notes
Plan Review Notes For Permit 03120481
Permit Number 03120481
Review Stop E
Sequence Number 1
Notes
Date Text
2003-12-23 00:00:00*********** UNSAT *****************
  
 1)NOTE; PLEASE MOVE SD SHOWN IN MASTER
 BEDROOM HALL INTO BEDROOM. NFPA-72, LS
 101 ETC. 8-1.4
  
 2)NOTE: PLEASE SEE PANEL SCHEDULE SHOWS
 PANEL AS 225A AND RISER SHOWS 200A.
  
 3)NOTE: PLEASE SEE NOTE FOR 210.12.
 WE ARE NOW UNDER THE 2002 NEC AND HAVE
 BEEN SINCE 7/1/03.REQUIREMENT HAS
 CHANGED.
  
 4)NOTE: PLEASE PROVIDE ROOM DESIGNATION
 ON PLANS.
  
 5)NOTE: PLEASE SEE THAT NOTES ARE STILL
 REFERENCING THE 1999 NEC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 PLEASE NOTE, IF PERMIT IS NOT ISSUED
 BY JAN 10TH, NOC WILL EXPIRE PER FS
 713. WORK MUST COMMENCE W/IN 90 DAYS
 OF RECORDING NOC.
 DATE ON NOC IS 10/10/03