| 2004-07-16 00:00:00 | ************** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE SEE ADDTIONAL SHEETS |
| | WHICH ARE SIGNED AND SEALED BY THE ARCH |
| | OF RECORD ARE REQUIRED TO HAVE TITLE |
| | BLOCK PER FAC 61G1-16.004 |
| | |
| | 2)NOTE: PLEASE CORRELATE A/C LOADS WITH |
| | AWG AND OCP. PLEASE SEE 424.3B |
| | PLEASE SEE 60A OCP W/ #8 AWG, 5KW W/ 60A |
| | OCP. ETC. |
| | |
| | 3)NOTE: PLEASE SEE LOAD CALCUALTIONS, |
| | MUST MEET 220.31B. |
| | A/C LOADS DERARTED, THIS IS NOT PERMITT- |
| | ED.PLEASE ADJUST |
| | |
| | 4)NOTE: PLEASE SEE ONLY ONE PANEL SCHEDU |
| | -LE WAS SUBMITTED. |
| | |
| | 5)NOTE: PLEASE SEE MAIN PANEL ALSO SHOWS |
| | AN ADDITIONAL FEED OUT OF THE TOP OF |
| | PANEL?? |
| | |
| | 6)NOTE: PLEASE SEE 210.52 FOR MISSING |
| | RECEPTS ON PLANS. |
| | |
| | 7)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | PLEASE SEE 2 MISSING AND REDLINED ON |
| | PLANS. |
| | |
| | 8)NOTE:PLEASE SHOW LOCATION OF SERVICE, |
| | PLANS SHOWS OLD METER LOCATION BUT NOTH- |
| | -ING SHOWN FOR NEW. |
| | |
| | 9)NOTE: PLEASE SEE ALL CONTINOUS LOADS |
| | ARE TO BE SHOWN AT 125%. PLEASE SEE |
| | POOL HEATER AND PUMP. |
| | |
| | PLEASE SEE ONE SET HAS SOME OF THESE |
| | ITEMS REDLINED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |