2003-12-22 00:00:00DENIED:
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
 1.ENERGY & MAUNAL J CALCULATIONS FOR
 THE ADDITIION.
  
 2.PROVIDE THE FOLLOWING EQUIPMENT
 INFORMATION:MAKE, MODEL, BTU'S OF THE
 AHU AND SEER OF THE CONDENSER UNIT.
  
 3.PLEASE PROVIDE THE DUCT/GRILLE SIZE,
 LAYOUT AND MATERIAL.PLEASE NOTE PER
 REVISION TO THE 2001 FBC(M) 601.4
 EFFECTIVE JUNE 30,2003, RETURN OR
 TRANSFER AIR REQUIRED FROM ROOMS
 SEPARATED BY A DOOR.SEE ATTACHED FOR
 SIZING REQUIREMENTS.
  
 4.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.