Plan Review Notes
Plan Review Notes For Permit 03120438
Permit Number 03120438
Review Stop E
Sequence Number 1
Notes
Date Text
2003-12-17 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE INDICATE THE SIZE OF THE
 EXISTING SERVICE.THE RISER STATES A 300
 AMP PANEL BUT THE FEED CONDUCTORS ARE
 RATED FOR 200 AMPS PER 310.15(B).
  
 2} PLEASE USE THE CALCULATION IN
 220.31(B), SHOW ENTIRE LOAD,EXISTING
 AND ADDITIONAL.
  
 3} PLEASE NOTE THE A/C LOAD MUST BE
 TAKEN AT 100%.(220.31(B)).
  
 4} NOTE #6 IS INCORRECT UNLESS THE
 CIRCUITS MENTIONED ARE ARC FAULT.SMOKE
 DETECTORS LOCATED IN BEDROOMS MUST
 COMPLY WITH 210.12 AND BE ARC FAULT
 PROTECTED.
  
 5} PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2',6',12' RULE PER 210.52,
 IN ALL ADDED SPACES.
  
 6} PLEASE NOTE MISSING OUTLET FOR
 A/C EQUIPMENT PER 210.63.
  
 7} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STAIRWAYS. 2-5.2.1.3
 3'FT FROM BATHS/KITCHENS.2-5.2.1.6
  
 8} PLEASE SHOW RECEPTACLES IN HALLWAYS
 TO COMPLY WITH 210.52(H).
  
 9} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210.52E
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718