| 2003-12-17 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE PROVIDE THE FOLLOWING |
| | INFORMATION,MAKE NECESSARY CHANGES TO |
| | PLANS AND RESUBMIT FOR REVIEW. |
| | |
| | 1} PLEASE INDICATE THE SIZE OF THE |
| | EXISTING SERVICE.THE RISER STATES A 300 |
| | AMP PANEL BUT THE FEED CONDUCTORS ARE |
| | RATED FOR 200 AMPS PER 310.15(B). |
| | |
| | 2} PLEASE USE THE CALCULATION IN |
| | 220.31(B), SHOW ENTIRE LOAD,EXISTING |
| | AND ADDITIONAL. |
| | |
| | 3} PLEASE NOTE THE A/C LOAD MUST BE |
| | TAKEN AT 100%.(220.31(B)). |
| | |
| | 4} NOTE #6 IS INCORRECT UNLESS THE |
| | CIRCUITS MENTIONED ARE ARC FAULT.SMOKE |
| | DETECTORS LOCATED IN BEDROOMS MUST |
| | COMPLY WITH 210.12 AND BE ARC FAULT |
| | PROTECTED. |
| | |
| | 5} PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2',6',12' RULE PER 210.52, |
| | IN ALL ADDED SPACES. |
| | |
| | 6} PLEASE NOTE MISSING OUTLET FOR |
| | A/C EQUIPMENT PER 210.63. |
| | |
| | 7} SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | IN THE VICINITY OF BEDROOMS AND CLOSE |
| | PROXIMITY OF STAIRWAYS. 2-5.2.1.3 |
| | 3'FT FROM BATHS/KITCHENS.2-5.2.1.6 |
| | |
| | 8} PLEASE SHOW RECEPTACLES IN HALLWAYS |
| | TO COMPLY WITH 210.52(H). |
| | |
| | 9} PLEASE NOTE FRONT AND REAR |
| | RECEPTS REQ`D PER 210.52E |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |