| 2004-01-20 00:00:00 | ************ UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE SEE THAT THERE ARE SOME |
| | ITEMS THAT STILL NEED TO CORRELATE. |
| | |
| | 2)NOTE: PLANS SHOW NEW PANEL "B" SCHED- |
| | -ULE, HOWEVER, DOES NOT CARRY OVER SOME |
| | OLD ITEMS. DRYER, WATER HEATER ETC. |
| | |
| | 3)NOTE: PLEASE ALSO SEE THAT WASHER AND |
| | DRYER ARE NOW BEING SHOWN AS GFI? |
| | |
| | 4)NOTE: PLEASE SEE 210.52D, 210.11C3, |
| | NO OTHER RECEPTS ARE PERMITTED TO BE ON |
| | BATH RECEPT CIRCUIT. |
| | |
| | 5)NOTE: PLEASE SEE PLANS NOW SUBMITTED |
| | SHOW A NEW RISER DIAGRAM. PLANS NOW |
| | SHOW A NEW/ EXST MAIN DISC. |
| | PLANS SHOW EXIST METER AND MAIN PANEL |
| | OUTSIDE? IS THIS PANEL "A"? PLEASE LABEL |
| | SHOW ON PLANS. |
| | |
| | 6)NOTE: MISSING EQUIPMENT GROUNDING |
| | CONDUCTORS BETWEEN MAIN DISC AND PANEL |
| | "A". 250.24,250.110,250.122 |
| | |
| | 7)NOTE: PLEASE SEE MIN LOADS REQ`D FOR |
| | WATER HEATER AND DRYER NOT SHOWN IN |
| | LOAD CALCS. 220.18 ETC |
| | |
| | 8)NOTE: PLEASE VERIFY WATER HEATER SHOWN |
| | IN CLOSET. WATER HEATER NOT PERMITTED IN |
| | AREA W/OUT PERMENANT BARRIER. 422.17 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | PLEASE REMOVE ALL OLD VOIDED SHEETS AND |
| | INSERT NEW SHEETS INTO TWO COMPLETE SETS |
| | FOR REVIEW/STAMPING. |