2004-01-20 00:00:00************ UNSAT *****************
  
 1)NOTE: PLEASE SEE THAT THERE ARE SOME
 ITEMS THAT STILL NEED TO CORRELATE.
  
 2)NOTE: PLANS SHOW NEW PANEL "B" SCHED-
 -ULE, HOWEVER, DOES NOT CARRY OVER SOME
 OLD ITEMS. DRYER, WATER HEATER ETC.
  
 3)NOTE: PLEASE ALSO SEE THAT WASHER AND
 DRYER ARE NOW BEING SHOWN AS GFI?
  
 4)NOTE: PLEASE SEE 210.52D, 210.11C3,
 NO OTHER RECEPTS ARE PERMITTED TO BE ON
 BATH RECEPT CIRCUIT.
  
 5)NOTE: PLEASE SEE PLANS NOW SUBMITTED
 SHOW A NEW RISER DIAGRAM. PLANS NOW
 SHOW A NEW/ EXST MAIN DISC.
 PLANS SHOW EXIST METER AND MAIN PANEL
 OUTSIDE? IS THIS PANEL "A"? PLEASE LABEL
 SHOW ON PLANS.
  
 6)NOTE: MISSING EQUIPMENT GROUNDING
 CONDUCTORS BETWEEN MAIN DISC AND PANEL
 "A". 250.24,250.110,250.122
  
 7)NOTE: PLEASE SEE MIN LOADS REQ`D FOR
 WATER HEATER AND DRYER NOT SHOWN IN
 LOAD CALCS. 220.18 ETC
  
 8)NOTE: PLEASE VERIFY WATER HEATER SHOWN
 IN CLOSET. WATER HEATER NOT PERMITTED IN
 AREA W/OUT PERMENANT BARRIER. 422.17
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
 PLEASE REMOVE ALL OLD VOIDED SHEETS AND
 INSERT NEW SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW/STAMPING.