Notes
Date Text
2003-12-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) SANITARY RISER DIAGRAM AND FLOOR PLAN
 DOES NOT MEET CODE REQUIREMENTS. SECTION
 909.1. ONLY THE FIXTURES WITHIN THE
 BATHROOM GROUP SHALL CONNECT TO THE WET-
 VENTED HORIZONTAL BRANCH DRAIN, ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE DOWN
 STREAM OF THE WET VENT. THE WASHMACHINE
 SHALL CONNECT DOWNSTREAM OF BATHROOM
 FIXTURES.
 2) SEPARATE GAS AND PLUMBING PERMITS ARE
 REQUIRED.
  