Plan Review Notes
Plan Review Notes For Permit 03120434
Permit Number 03120434
Review Stop E
Sequence Number 1
Notes
Date Text
2003-12-22 00:00:00************** UNSAT **************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM/
 PLANS AND PANEL SCHEDULES. THERE IS ONE
 SET HIGHLIGHTED WITH MANY ITEMS SHOWN.
  
 2)NOTE: PLEASE INCLUDE ALL MIN CIRCUIT-
 -ING ON PANEL SCHEDULES. PLEASE ALSO
 INCLUDE LOAD SHOWNS ON LOAD CALCULATIONS
 IE;SM APPL, WASHER ETC ETC. 210.11,
 220.16,220.18 ETC.
  
 3)NOTE: PLEASE SEE MISSING REQ'D ARC
 FAULT PROTECTION PER 220.12
  
 4)NOTE: PLEASE SEE MISSING BATH CIRCUIT
 PER 210.52D, 210.11C3 MIN #12 AND 20A.
  
 5)NOTE: PLEASE INCLUDE ALL CONDUCTOR
 SIZES ON RISER DIAGRAM AFTER CORRELATING
 PLANS.
  
 6)NOTE: PLEASE CLARIFY BRKR SHOWN TO
 "GARAGE" ? DETACHED?
  
 7)NOTE: PLEASE SEE 200A BRKR SHOWN AS
 AND 8-POLE AND 100A PANEL SHOWN W/ A
 3-POLE BRKR??
  
 8)NOTE: PLEASE SEE 210.8 FOR ALL RECEPTS
 IN GARAGE AS GFI.
  
 9)NOTE: PLEASE SEE MISSING SD REQ'D
 OUTSIDE BEDROOM.
  
 10)NOTE: PLEASE INCLUDE NEW FOOTER STEEL
 AS PART OF THE GROUNDING ELECTRODE
 SYSTEM. 250.50
  
 11)NOTE: THIS IS JUST A NOTE; IF THERE
 IS GOING TO BE ANY NEW LV(TV,PHONE,ETC)
 PLEASE SHOW ON PLANS. IF NOT SEPARATE
 PLANS WILL NEED TO COME BACK IN WHEN
 LV PERMIT IS APPLIED FOR.
  
 12)NOTE: PLEASE CLARIFY PANEL SHOWN
 STICKING OUT INTO DOORWAY? IS THIS
 MOVING? BEING RELOCATED?
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND MAKE ALL CORRECTIONS.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  