Plan Review Notes
Plan Review Notes For Permit 03120434
Permit Number 03120434
Review Stop B
Sequence Number 1
Notes
Date Text
2003-12-30 00:00:001.905.2.1 RESIDENTIAL SMOKE ALARMS:
 NFPA 72.A-8-1.2.1 IN FAMILY UNITS WITH
 MORE THAN ONE BEDROOM AREA OR WITH BED-
 ROOMS ON MORE THAN ONE FLOOR, MORE THAN
 ONE SMOKE DETECTOR IS REQUIRED.
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 3. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
 4.A SEPERATE ROOFING PERMIT IS
 REQUIRED.
 5. STORM PANEL PRODUCT APPROVALS NOT
 LISTED ON THE FBC APPROCAL SITE.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ART LANGE
 BUILDING PLANS EXAMINER
 561-805-6672