Plan Review Notes
Plan Review Notes For Permit 03120429
Permit Number 03120429
Review Stop P
Sequence Number 1
Notes
Date Text
2003-12-18 00:00:00DENIED
 REFERENCE: FBC-2001 242.2 SWIMMING POOLS
 FLA. ADMIN. CODE
 FLA. STATUTES
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001 424.2.7.2 PUMPS AND EQUIP-
 MENT SHALL BE MOUNTED ON A SUBSTANTIAL
 BASE IN A MANNER THAT WILL ELIMINATE
 STRAIN ON PIPING. SLAB SHALL BE A NOMIN-
 AL 4" THICK. (DETAIL)
 2) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 3) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 4) FBC-2001 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 5) ENGINEERS SHALL SIGN THEIR NAME ON
 THEIR SEAL PER FAC 61G15-23.002(1) AND
 FS 471.025. RULING BY FBPE STATES THAT
 THE MINIMUM OF A FIRST AND LAST NAME
 REQUIRED.
  
 REVIEW BY KEN STEVENS