| Plan Review Notes For Permit 03120425 |
| Permit Number |
03120425 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-03-19 00:00:00 | | | | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW ON NEXT REVISION OR ON AS-BUILTS. | | | | | | 1} THE OCP AND WIRE SIZE FOR THE SUB | | | PANEL FEEDER ON PANEL "A" SCHEDULE IS | | | INCORRECT, LISTED AS 15AMP SINGLE POLE | | | & #14 WIRE, RISER INDICATES 60 AMP/#6 | | | WIRE. | | | | | | 2} SHOW COMPLIANCE WITH 250.122 FOR | | | PANEL "B" FEED. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|