2003-12-30 00:00:00DENIED:
 RETURN AIR (JUMPERS) NOT SIZED PROPERLY.
 7" SUPPLY AIR REQUIRES A 9" RETURN AIR
 JUMPER WITH 1" CLEAR UNDERCUT OF THE
 DOOR.THE MASTER SUITE HAS A 12" MAIN
 SUPPLY AIR & REQUIRES A 15" RETURN AIR
 JUMPER WITH A 1" CLEAR UNDERCUT OF THE
 DOOR.PLEASE REVISE PLANS TO REFLECT
 PROPER SIZING AND SEE ATTACHED SCHEDULE
 FOR FUTURE SIZING REQUIREMENTS.
  