| Plan Review Notes For Permit 03120425 |
| Permit Number |
03120425 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-30 00:00:00 | DENIED: | | | RETURN AIR (JUMPERS) NOT SIZED PROPERLY. | | | 7" SUPPLY AIR REQUIRES A 9" RETURN AIR | | | JUMPER WITH 1" CLEAR UNDERCUT OF THE | | | DOOR.THE MASTER SUITE HAS A 12" MAIN | | | SUPPLY AIR & REQUIRES A 15" RETURN AIR | | | JUMPER WITH A 1" CLEAR UNDERCUT OF THE | | | DOOR.PLEASE REVISE PLANS TO REFLECT | | | PROPER SIZING AND SEE ATTACHED SCHEDULE | | | FOR FUTURE SIZING REQUIREMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|