| Plan Review Notes For Permit 03120422 |
| Permit Number |
03120422 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-03-19 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} AN EQUIPMENT GROUND PER 250.122 IS | | | REQUIRED FROM PANEL "A" TO THE SUB- | | | PANEL. | | | | | | 2} THE SUB PANEL FEEDER ON THE PANEL"A" | | | SCHEDULE IS LISTED AS #14 ON A 15AMP | | | SINGLE POLE BREAKER. THE PREVIOUSLY | | | SUBMITTED PLAN WAS RETURNED TO THE | | | ARCHITECT WITH A COMMENT ABOUT THIS | | | FEEDER BEING A 2 POLE 20AMP. PEASE | | | INDICATE THE CORRECT OCP AND FEEDER | | | SIZE ON PLANS. | | | | | | 3} VERIFY THE LOCATION OF THE POOL | | | PANEL(SUB PANEL). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|