| Date |
Text |
| 2004-02-23 00:00:00 | *************** UNSAT ************* | | | | | | 1)NOTE: PLEASE SEE ORIGINAL REDLINED | | | NOTES. | | | PLEASE CORRELATE PANEL SCHEDULES WITH | | | RISER DIAGRAM. 200A PANEL SHOWS A 2P20A | | | BRKR FEEDING 60A SUB PANEL? | | | PLEASE SEE LOAD. | | | | | | 2)NOTE: PLEASE REVISE LOAD CALCULATIONS | | | TO INCLUDE NEW LOADS. | | | LOADS WERE NOT ADDED TO 200A PANEL/SERV. | | | | | | 3)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR FROM 200A PANEL | | | TO 60A SUB PANEL. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|