| Plan Review Notes For Permit 03120405 |
| Permit Number |
03120405 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-19 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT 1.1 PER TABLE 403.1 A DRINKING | | | FOUNTAIN AND A SERVICE SINK IS REQUIRED. | | | 2) BOTH SANITARY AND WATER RISER DIA- | | | GRAMS ARE REQUIRED. 104.3.1.1 | | | 3) SHT 1.1 H/C TOILET ELEVATIONS AND | | | FLOOR PLAN. SHOW CLEAR FLOOR SPACE FOR | | | FIXTURES 11-4.22.3, W/C HEIGHT 11-4.16.3 | | | LAV HEIGHT & CLEARANCES 11-4.19.2,EX- | | | POSED PIPES AND SURFACES 11-4.19.4. | | | 4) SUBMIT A DETAIL FOR THE DRINKING | | | FOUNTAIN REQUIRED BY TABLE 403.1 THAT | | | COMPLY WITH 11-4.15 AND ALL SUBSECTIONS. | | | ALSO SHOW COMPLIANCE WITH 11-4.1.3(10)(A | | | PROVISIONS FOR THOSE WHO HAVE DIFFICULTY | | | BENDING OR STOOPING. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|