Plan Review Notes
Plan Review Notes For Permit 03120403
Permit Number 03120403
Review Stop E
Sequence Number 1
Notes
Date Text
2004-02-05 00:00:00**************** UNSAT **********
 ********* NEED INFO ******************
  
 1)NOTE: PLEASE PROVIDE LAYOUT FOR
 ELECTRICAL WORK TO BE PERFORMED.
  
 2)NOTE: UPON FIELD EVALUATION INSPECTION
 OF SITE. DEMO WORK HAS ALREADY COMMENCED
 AND NUMEROUS LOCATIONS OF WIRING AND
 WIRING DEVICES ARE EXPOSED AND MUST
 BE "SAFED" OFF. PLEASE SECURE MAIN
 ELECTRICAL ROOM AND LOCK ALL ELECTRICAL
 EQUIPMENT AS REQ'D UNDER NEC. 110.27
 ETC.
  
 3)NOTE: PLEASE PROVIDE LAYOUT FOR NEW
 TEMPORARY LIGHTING TO BE INSTALLED.
 PER ART 527 OF THE 2002 NEC.
 THE TEMPORARY WIRING OF LTS ON SITE
 ALSO DONE W/OUT PERMITS; DO NOT MEET
 REQUIREMENTS OF NEC.
  
 4)NOTE: AREA ON PLANS THAT CALL TO HAVE
 WALLS DEMOLISHED SEEM TO HAVE ELECTRICAL
 EQUIPMENT ATTACHED. PLEASE PROVIDE
 INFORMATION ON THIS AND/OR REMOVE FROM
 SCOPE OF WORK.
  
 5)NOTE: PLEASE NOTE: FROM THE ON-SITE
 INSPECTION WEST AREA OF PARKING GARAGE
 DIRECTLY BELOW UNFINISHED WEST TOWER.
 A SUBSTANTIAL WATER LEAK HAS CORRODED
 AND RUSTED SOME FEEDERS CONDUITS EXPOSE-
 ING FEEDERS. THIS MUST BE REPAIRED ASAP
 (30DAYS).
  
 PLEASE HAVE AN ELECTRICAL CONTRACTOR
 APPLY FOR PERMIT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]