Plan Review Notes
Plan Review Notes For Permit 03120391
Permit Number 03120391
Review Stop E
Sequence Number 3
Notes
Date Text
2004-06-11 00:00:00*********** UNSAT ****************
  
 PLEASE SEE SOME COMMENTS FROM PREVIOUS
 REVIEW HAS NOT BEEN ADDRESS.
  
 1)NOTE: NOTE #1 OK
  
 2)NOTE: NOTE #2 OK
  
 3)NOTE: NOTE #3 PLEASE SEE LICENSE #'S
 HAVE NOW BEEN ADDED TO TITLE BLOCK BUT
 DO NOT CORRELATE WITH DBPR FOR CORRECT
 #'S. PER CONVERSATION WITH DBPR/ ONE
 COPY IS TO BE SENT OFF TO STATE FOR
 REVIEW.
  
 4)NOTE: NOTE #4 NO PLEASE SEE PLANS,
 210.52C1
  
 5)NOTE: NOTE #5 OK
  
 6)NOTE: NOTE #6 OK, NOTED ON PLANS.
  
 7)NOTE: NOTE #7 NO. PLEASE ALSO SEE
 PLANS NOW CONTAIN TWO DIFFERENT SET OF
 LOAD CALCULATIONS. PLEASE REMOVE OLD
 AND REVISE NEW.
 PLEASE ALSO SEE LOAD CALCULATIONS DO NOT
 INDICATE LOADS FOR SPA TUB/ HEAT AS
 NOTED ON PLANS?
 215.5/220
  
 8)NOTE: PLEASE SEE NOTE # 9 ON ELECT-
 -RICAL GENERAL NOTES, MENTIONS ALL WIRE
 TO BE #12. PANEL SCHEDULE INDICATES
 #14
  
 THIS IS ONLY GIVEN AS A NOTICE.
 PLEASE SEE FS 553.80(2)(B) ATTACHED.
 PLEASE ADDRESS ALL COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]