| 2004-05-20 00:00:00 | *********** UNSAT ******************* |
| | |
| | 1)NOTE: PLEASE REMOVE EQUIPMENT GROUND- |
| | -ING CONDUCTOR BETWEEN METER AND MAIN |
| | DISCONNECT. NOT PERMITTED. 250.6,250.24 |
| | |
| | 2)NOTE: PLEASE INCLUDE FOOTER STEEL AS |
| | PART OF THE GRND ELEC SYSTEM. PER 250.50 |
| | |
| | 3)NOTE: PLEASE SEE MISSING LICENSE # |
| | ON TITLE BLOCK PER 61G1-16.004 AND FS |
| | 481.219 |
| | |
| | 4)NOTE: PLEASE SEE 210.52C1 FOR KITCHEN |
| | COUNTERSPACE RECEPTS. |
| | |
| | 5 NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 6)NOTE: PLEASE LIST THE REQ'D ARC FAULT |
| | PROTECTED CIRCUITS ON PANEL SCHEDULE. |
| | PER 210.12 2002 NEC. |
| | PLANS SHOW AFB FOR RECEPTS, REQ'D FOR |
| | SD'S , FANS, LTS ETC IN BEDRMS. |
| | |
| | 7)NOTE: PLEASE SHOW LOAD CALCUALTIONS |
| | PER NEC 220. |
| | PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |