2004-05-20 00:00:00*********** UNSAT *******************
  
 1)NOTE: PLEASE REMOVE EQUIPMENT GROUND-
 -ING CONDUCTOR BETWEEN METER AND MAIN
 DISCONNECT. NOT PERMITTED. 250.6,250.24
  
 2)NOTE: PLEASE INCLUDE FOOTER STEEL AS
 PART OF THE GRND ELEC SYSTEM. PER 250.50
  
 3)NOTE: PLEASE SEE MISSING LICENSE #
 ON TITLE BLOCK PER 61G1-16.004 AND FS
 481.219
  
 4)NOTE: PLEASE SEE 210.52C1 FOR KITCHEN
 COUNTERSPACE RECEPTS.
  
 5 NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 6)NOTE: PLEASE LIST THE REQ'D ARC FAULT
 PROTECTED CIRCUITS ON PANEL SCHEDULE.
 PER 210.12 2002 NEC.
 PLANS SHOW AFB FOR RECEPTS, REQ'D FOR
 SD'S , FANS, LTS ETC IN BEDRMS.
  
 7)NOTE: PLEASE SHOW LOAD CALCUALTIONS
 PER NEC 220.
 PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  