| Plan Review Notes For Permit 03120391 |
| Permit Number |
03120391 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-02-05 00:00:00 | DENIED | | | | | | 1) BUCK FASTENING DETAILS ON A-7 FOR | | | ENTRY DOOR SPECIFIES 1X4 PT BUCK AND | | | STATES THAT FRAME WILL BE ATTACHED TO | | | BUCK WITH SCREWS WITH 3/4" EMBEDMENT | | | INTO THE BUCK. FBC 1707.4.4.2 REQUIRES | | | THE FRAME TO BE FASTENED THROUGH THE | | | BUCK INTO THE STRUCTURAL SUBSTRATE. | | | PLEASE CORRECT. ITEM #8 | | | | | | 2) THE PRODUCT APPROVAL FOR THE DOUBLE | | | ELLIPTICAL TOP ENTRY DOORS SUBMITTED, | | | DOES NOT COMPLY WITH RULE 9B-72. SEE | | | RULE AND SUBMIT ALL REQUIRED PAPERWORK. | | | DRAWINGS MUST MATCH DOORS, QUALITY | | | ASSURANCE IS REQUIRED, ETC. ITEM #10 | | | | | | 3) TWO COPIES OF THE STATE PRODUCT | | | APPROVAL COVER SHEETS IS REQUIRED. | | | ITEM #9 | | | | | | 4) FLOOR PLANS AND ELEVATIONS DO NOT | | | INDICATE THAT ELLIPTICAL TOPS OF FRENCH | | | DOOR AND CASEMENT WINDOWS HAS BEEN | | | ELIMINATED. ITEM #11 | | | | | | 5) PRODUCT APPROVAL FOR THE SINGLE SWING | | | DOOR AT THE GARAGE IS FOR A DOUBLE DOOR | | | THAT REQUIRES IMPACT PROTECTION. SUBMIT | | | APPROPRIATE PRODUCT APPROVALS. ITEM #14 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|