Plan Review Notes
Plan Review Notes For Permit 03120391
Permit Number 03120391
Review Stop B
Sequence Number 1
Notes
Date Text
2004-01-13 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A SEPARATE PERMIT IS REQUIRED FOR THE
 POOL.
  
 3) SUBMIT 2 COPIES OF A RECENT SURVEY.
  
 4) FBC TABLE 1604.1 REQUIRES A LIVE LOAD
 OF 10 PSF FOR ATTICS WITHOUT STORAGE AND
 30 PSF FOR ATTICS WITH STORAGE. PLEASE
 NOTE THIS ON THE PLANS FOR THE BOTTOM
 CORD LIVE LOAD OF THE TRUSSES.
  
 5) SUBMIT SPECIFICATIONS FROM WINDOW
 MANUFACTURER INDICATING THE CLEAR
 OPENING SIZES OF THE CASEMENT WINDOWS IN
 THE SLEEPING ROOMS FOR DETERMINING
 COMPLIANCE WITH FBC 1005.4 FOR EMERGENCY
 EGRESS.
  
 6) SUBMIT MANUFACTURER,S SPECIFICATIONS
 AND LISTING INFORMATION FOR THE PREFAB
 FIREPLACE AND FLUE PIPE.
  
 7) THE CITY OF WPB AMENDMENTS TO FBC
 TABLE 2306.1 REQUIRES THE ROOF SHEATHING
 TO BE NAILED 4"OC AT EDGES AND 6"OC IN
 ZONE 3 WHICH INCLUDES THE OUTSIDE
 CORNERS OF HIP ROOFS. SEE FBC FIGURE
 1606.2(C). PLEASE REVISE THE NOTES ON
 A6, S2 AND S3.
  
 8) FBC 1707.4.4.2 REQUIRES DOOR FRAMES
 TO BE ATTACHED THROUGH THE BUCK AND INTO
 THE STRUCTURAL SUBSTRATE WHEN THE BUCK
 IS LESS THAN 1-1/2". PLEASE REVISE THE
 DOOR BUCK DETAIL ON A7. NOTE THE PRODUCT
 APPROVALS FOR THE PELLA DOORS REQUIRE
 2X BUCKS.
  
 9)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 10) SUBMIT PRODUCT APPROVALS FOR DOUBLE
 OUTSWING ELLIPTICAL TOP WOOD DOORS WITH
 SIDELITES FOR THE FRONT ENTRY DOORS AS
 SHOWN ON THE PLANS.
  
 11) SUBMIT PRODUCT APPROVALS FOR THE
 ELLIPTICAL TOP GLAZED FRENCH DOORS AND
 THE ELLIPTICAL TOP VENTED CASEMENT
 WINDOWS AS SHOWN ON THE PLANS.
  
 12) CLARIFY WHY THE DRAWINGS FOR THE
 NON-IMPACT OPERABLE CASEMENT WINDOWS
 WAS SUBMITTED. (DRAWING #1161)
  
 13) SUBMIT PRODUCT APPROVALS FOR THE
 GLASS BLOCK.
  
 14) SUBMIT PRODUCT APPROVALS FOR THE
 SINGLE OUTSWING SOLID GARAGE DOOR.
  
 15) SUBMIT A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS INDICATING
 HOW AND WHERE THEY WILL BE INSTALLED.
 NOTE: GLASS BLOCK COMPLYING WITH FBC
 SECTION 2112 DO NOT HAVE TO BE PROTECTED
  
 16) SPECIFY THE UPLIFT CAPACITIES AND
 THE WELD TYPES FOR THE STEEL COLUMNS ON
 S3.
  
 17) ON SHEET S4 PLEASE CHANGE THE
 REFERENCES FROM SBC TO FBC AND CORRECT
 THE MEAN ROOF HEIGHT TO CONCUR WITH THE
 ONE LISTED ON A1.
  
 18)1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
 PLEASE REVISE THE VALUES IN THE TRUSS
 ANCHOR SCHEDULE & UPDATE THE CONNECTORS
 TO THOSE IN CURRENT CATALOGS WITH STATE
 PRODUCT APPROVAL.
  
 19) SUBMIT STATE PRODUCT APPROVAL FOR
 TRUSS CONNECTORS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714