| 2003-12-17 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 424.2 SWIMMING POOLS |
| | FLA. ADMIN. CODE |
| | FLA. STATUTES |
| | |
| | A) FOLLOWING INFORMATION REQUIRED FOR |
| | POOL PLANS AND PLAN REVIEW: |
| | B) PLEASE ADJUST YOUR NOTES, DETAILS, OR |
| | SUBMITTALS TO REFLECT THE FOLLOWING IN- |
| | FORMATION REQUIRED FOR PLAN REVIEW |
| | 1) COMPLY WITH FBC-2001 SEC 424.2 |
| | PRIVATE SWIMMING POOLS. |
| | 2) FBC-2001 SEC 424.2.6.1 ENGINEERING |
| | DESIGN, CONSTRUCTION AND WORKMANSHIP. |
| | ANSI/NSPI-5. (ADD TO NOTES) |
| | 3) FBC-2001 SEC 424.2.6.6 ENTRAPMENT |
| | PROTECTION FOR SUCTION INLETS. (DETAIL) |
| | 4) FBC-2001424.2.6.6.2 SHOW COMPLIANCE |
| | WITH ANSI/ASME A112.19.8M. PROVIDE MODEL |
| | NUMBER AND MANUF INFO FOR VAC LOCK. |
| | (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES) |
| | 5) FBC-2001424.2.6.6.3 (1,2,3) ENTRAP- |
| | MENT AVOIDANCE. (DETAIL) |
| | 6) FBC-2001424.2.6.6.4 MINIMUM OF TWO |
| | SUCTION INLETS SHALL BE PROVIDED FOR EA |
| | PUMP. SEPARATED BY A MINIMUM OF 3 FEET |
| | OR LOCATED ON TWO DIFFERENT PLANES. |
| | (DETAIL) |
| | 7) FBC-2001424.2.6.6.5 WHERE PROVIDED, |
| | THE VACUUM OR PRESSURE CLEANER FITTING |
| | SHALL BE LOCATED AT LEAST 6" AND NOT |
| | GREATER THAN 12" BELOW THE MINIMUM OPER- |
| | ATING WATER LEVEL OR AS AN ATTACHMENT TO |
| | THE SKIMMER. |
| | 8) FBC-2001424.2.7.1 POOL CIRCULATING |
| | PUMPS SHALL BE EQUIPPED ON THE INLET |
| | SIDE WITH AN APPROVED TYPE HAIR AND LINT |
| | STRAINER WHEN USED WITH A PRESSURE FIL- |
| | TER. (DETAIL OR ADD TO NOTES) |
| | 9) FBC-2001 424.2.7.2 PUMPS AND EQUIP- |
| | MENT SHALL BE MOUNTED ON A SUBSTANTIAL |
| | BASE IN A MANNER THAT WILL ELIMINATE |
| | STRAIN ON PIPING. SLAB SHALL BE A NOMIN- |
| | AL 4" THICK. (DETAIL) |
| | 10) FBC-2001 424.2.8.1 VALVES SHALL BE |
| | MADE OF MATERIALS THAT ARE APPROVED IN |
| | THE FLA BLDG CODE, PLUMBING. THEY WILL |
| | BE READILY ACCESSIBLE FOR MAINT. AND RE- |
| | MOVAL. SEC 424.2.8.2 FULL WAY VALVES |
| | SHALL BE INSTALLED TO INSURE PROPER FUN- |
| | CTION OF THE FILTRATION AND PIPING SYS- |
| | TEM. SEC 424.2.8.3 WHERE CHECK VALVES |
| | ARE INSTALLED THEY SHALL BE OF THE SWING |
| | OR VERTICAL CHECK PATTERNS. SEC 424.2.8. |
| | 4 COMBINATION VALVES SHALL REQUIRE APP- |
| | ROVAL OF THE ADMINISTRATIVE AUTHORITY |
| | PRIOR TO THEIR INSTALLATION. |
| | 11) FBC-2001 424.2.9 WATER SUPPLY, LOCAL |
| | ORD. #2853-95, BACKFLOW REQUIRED ON |
| | WATER SERVICE. (ADD TO NOTES) |
| | 12) FBC-2001 424.2.12.1 PRESSURE TESTS. |
| | PER MANUFACTURE RECOMMENDATIONS, NO AIR |
| | TEST SHALL BE APPROVED FOR PVC PIPE AND |
| | FITTINGS. (ADD TO NOTES) |
| | 13) FBC-2001 424.2.13.2JOINTS AND CON- |
| | NECTIONS, FBC PLMG SEC 605.21, PURPLE |
| | PRIMER REQUIRED ON PVC PIPING. (ADD TO |
| | NOTES) |
| | ******IF A POOL HEATER IS INSTALLED***** |
| | 14) FBC-2001 424.2.14.1 SWIMMING POOL |
| | WATER HEATERS SHALL BEAR THE LABEL OF A |
| | RECOGNIZED TESTING AGENCY. MANUFACTURE |
| | SHEETS REQUIRED. (SUBMITTAL) |
| | 15) FBC-2001 424.2.14.2 WATER RETENTION, |
| | PROVIDE A POSITIVE MEANS OF RETAINING |
| | WATER IN THE HEATER WHEN PUMP IS SHUT |
| | OFF. (MANUFACTURE CUT SHEETS SUBMITTAL) |
| | 16) FBC-2001 424.2.14.4 CONNECTIONS, ALL |
| | WATER HEATING EQUIPMENT SHALL BE INSTAL- |
| | LED WITH FLANGES OR UNION CONNECTIONS |
| | ADJACENT TO THE HEATER. (ADD TO NOTES) |
| | 17) FBC02001 424.2.15 GAS PIPING SHALL |
| | COMPLY WITH FBC FUEL GAS. SEPARATE PLANS |
| | AND PERMIT REQUIRED. |
| | 18) SUBMIT A POOL LAYOUT WITH DRAINS, |
| | RETURNS, SKIMMERS, VENTS, VACUUM (IF |
| | APPLICABLE), PIPING WITH PIPE SIZE FROM |
| | FITTINGS TO POOL EQUIPMENT PAD, ECT. |
| | 19) SUBMIT A PIPING SCHEMATIC FOR POOL |
| | EQUIPMENT SHOWING ALL POOL EQUIPMENT, |
| | PUMP, FILTER, HEATER (WITH BYPASS), |
| | VALVES (AS REQUIRED), LINES FROM MAIN |
| | DRAINS, SKIMMER, INLETS, VAC LINE ECT. |
| | 20) SUBMIT A POOL SPECIFICATION LIST |
| | SHOWING POOL SIZE, POOL DEPTH, PERIMETER |
| | VOLUME (GALLONS), SURFACE AREA SQ. FT., |
| | TURNOVER TIME, PUMP SIZE HP, POOL FILTER |
| | NUMBER OF INLETS, SKIMMER #, POOL HEATER |
| | VACUUM LINE, CHLORINE DISPERSER ECT. |
| | 21) SUBMIT A DETAIL FOR HYDROSTATIC |
| | RELIEF PER 424.2.21.4 |
| | 22) INDICATE HOW THE WASTE WATER WILL BE |
| | DISPOSED PER 424.2.10 |
| | 23) WATER VELOCITY SHALL NOT EXCEED 10 |
| | FEET PER SECOND. 424.2.6.3. |
| | 24) MORE COMMENTS MAY BE REQUIRED BASED |
| | ON INFORMATION SUBMITTED FOR NEXT REVIEW |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL |
| | REVIEW BY KEN STEVENS |