Plan Review Notes
Plan Review Notes For Permit 03120302
Permit Number 03120302
Review Stop E
Sequence Number 1
Notes
Date Text
2003-12-16 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE HAVE PLANS SIGNED, DATED
 AND SEALED BY THE ENGINEER OF RECORD.
 PER FS 471.025
 PLEASE PROVIDE ALL LICENSE #S ON TITLE
 BLOCK. PLEASE SEE FAC CODE AND FS.
 61G15-23.002 AND 471.025
  
 2)NOTE: PLEASE SEE THAT THERE IS NOT
 ENOUGH INFORMATION FOR REVIEW OF PROPOS-
 -ED NEW INGROUND SPA/SWIM UNIT?
 NO LOAD, NO WIRING DIAGRAM, NO LOAD CALC
 AND OCP FROM EXISTING PANEL??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  