Plan Review Notes
Plan Review Notes For Permit 03120255
Permit Number 03120255
Review Stop E
Sequence Number 4
Notes
Date Text
2004-04-19 00:00:00******** UNSAT *********
  
 1)NOTE: PLEASE SEE NO NEW ELECTRICAL
 SHEETS WERE SUBMITTED TO ADDRESS COMMENT
 -S GIVEN ON 3/4/04.
 PLEASE SEE FS 481.219 FOR REQ'D CERTIF-
 -ICATE OF AUTHORIZATION #.
 PLEASE SEE 61G1-16.004, ALL LICENSE
 #'S ARE REQ'D TO BE ON TITLE BLOCK.
  
 2)NOTE: PLEASE CORRECT CIRCUITING FOR
 EM LTS WHEN REVISING SHEET. 700.12E
 LETTER FROM ARCH WAS NOTED.
  
 COMMENT # 1 MUST BE ADDRESSED.
  
 **PLEASE REMOVE ALL OLD/ VOIDED SHEETS
 AND INSERT NEW CORRECT SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  