| Plan Review Notes For Permit 03120255 |
| Permit Number |
03120255 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-04-03 00:00:00 | | | | AS PER THE PREVIOUS REVIEWS THE | | | ARCHITECT FAILED TO RECIRCUIT THE | | | EMERGENCY/EXIT LIGHTS TO MEET THE | | | INTENT OF ARTICLE 700.12(E), ATTACHED. | | | THE EM/EXIT LIGHTS MUST BE FED FROM THE | | | LOCAL BRANCH LIGHTING CIRCUIT. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|