 AS PER THE PREVIOUS REVIEWS THE
 ARCHITECT FAILED TO RECIRCUIT THE
 EMERGENCY/EXIT LIGHTS TO MEET THE
 INTENT OF ARTICLE 700.12(E), ATTACHED.
 THE EM/EXIT LIGHTS MUST BE FED FROM THE
 LOCAL BRANCH LIGHTING CIRCUIT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  