Plan Review Notes
Plan Review Notes For Permit 03120255
Permit Number 03120255
Review Stop P
Sequence Number 2
Notes
Date Text
2004-02-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FLORIDA ADMIN. CODE
 FLORIDA STATUTES
  
 COMMENTS NOT ADDRESSED FROM FIRST REVIEW
 NUMBERS TO REMAIN THE SAME FOR CLAIRITY.
 3) CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE FOR SIZING OF GREASE INTER-
 CEPTOR. WASTE ORD #2938-96 (561) 837-
 4074. NEED COPY OF APPROVAL SHEET REC'D
 FROM R. COMPO.
 4) SHT 3 OF 4 FLOOR SINK STILL REQUIRED
 FOR ITEM #10. CHANGE WAS MADE TO MOP
 SINK NOT SLOP SINK (#10).
 5) SHT 3 OF 4 GREASE RISER DIAGRAM, A
 VENT IS REQUIRED FOR THE MOP SINK, SECT-
 ION 901.2.1 - VENT CAN NOT COME OUT OF
 DRAIN AS SHOWN. SEE RED LINE CORRECTION
 FOR PROPER VENTING.
 6) FIRM LICENSE NUMBER REQUIRED PER FAC
 61G1-16.004(2) & FS 481.219 (SEE SHEETS
 1 OF 4 & 2 OF 4 - PINE TREE DESIGN) -
 CERTIFICATE OF AUTHORIZATION NUMBERS ARE
 REQUIRED FOR ALL FICTICIOUS BUSINESSES.
 7) THE FOLLOWING INFORMATION IS REQUIRED
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. (SECTION OF PIPE BETWEEN
 THE RISE TO #7 STEAM TABLE AND #2 FIRST
 FRYER HAS NO LENGTH SHOWN) - SUBMIT A
 NEW SHEET WITH NEW RISER ON PLAN AND NOT
 TAPED ON EXISTING SHEET.
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2 - THE
 MANUF. SHEET FOR THE RICE COOKER AND THE
 WATER HEATER HAVE NOT BEEN SUBMITTED.
 THE MANUF. SHEETS FOR THE STEAM TABLE,
 THE SALAMANDER, & DEEP FRYERS DO NOT
 SHOW THE BTU'S/HR REQUIRED TO VERIFY
 PIPE SIZE.
 F. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2. - A
 SITE PLAN FOR THIS SPACE IS REQUIRED TO
 SHOW LOCATION AS REQUIRED. - MORE INFOR-
 MATION THAN SUBMITTED IS REQUIRED.
 G. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58.IF NEAR THE
 PARKING AREA OR ROAD WAY PROTECTION OF
 THE TANKS IS REQUIRED. SUBMIT DETAILS.
 H. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. - NO UNION
 IS SHOWN ON RISER DIAGRAM.
 ********NEW COMMENT FOR GAS PERMIT******
 INFORMATION FOR GAS PERMIT CAN BE SUB-
 MITTED AT TIME OF GAS PERMIT APPLICATION
 AND CAN BE OMITTED FROM THESE PLANS IF
 REQUESTED. - THE RISER DIAGRAM AND ALL
 MANUF SHEETS ECT WILL BE REQUIRED WHEN
 APPLYING FOR GAS PERMIT. OTHERWISE ALL
 INFORMATION WILL BE REQUIRED AT TIME OF
 RESUBMITTING PLANS.
  
 REVIEW BY KEN STEVENS