2004-03-04 00:00:00HVAC EXISTING REVISED O.A. CALCS ON PLAN
 SHEET 2 OF 4.SEPARATE PERMIT REQUIRED
 FOR THE HOOD, FIRE SUPPRESSION &
 WALK-IN COOLERS.
  
 PLEASE NOTE - EXHAUST TERMINATION FOR
 THE GREASE DUCT SHALL BE A MINIMUM OF
 10 FT FROM ADJACENT PROPERTY LINES,
 CONTINGUOUS BUILDINGS AND AIR INTAKES.
 2001 FBC(M) 506.3.14.3.