Plan Review Notes
Plan Review Notes For Permit 03120255
Permit Number 03120255
Review Stop P
Sequence Number 1
Notes
Date Text
2004-01-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FLA. ADMIN. CODE
 FLA. STATUTES
  
 1) SHT 1 OF 4, SPECIFICATION WORKSHEETS
 REFERED TO ON THE DEPT. OF BUSINESS REG-
 ULATION STAMP, COMMENT #3, SHALL BE SUB-
 MITTED WITH PLANS FOR REVIEW. SECTION
 104.2.1.
 2) AN RPZ BACKFLOW IS REQUIRED ON WATER
 SERVICE TO SPACE. SECTION 608.13.2.
 3) CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE FOR SIZING OF GREASE INTER-
 CEPTOR. WASTE ORD. #2938-96. (561) 837-
 4074.
 4) SHT 3 OF 4 FLOOR SINKS ARE REQUIRED
 FOR ITEMS 9 & 10, (3 COMP. SINK & SLOP
 SINK). HUB DRAINS ARE APPROVED FOR
 CLEAR WATER WASTE ONLY. SECTION 802.3
 5) SHT 3 OF 4 GREASE RISER DIAGRAM, A
 VENT IS REQUIRED FOR THE MOP SINK, SECT-
 ION 901.2.1
 6) FIRM LICENSE NUMBER REQUIRED PER FAC
 61G1-16.004(2) & FS 481.
 7) FOLLOWING INFORMATION REQUIRED FOR
 GAS PERMIT APPLICATION.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. TYPE OF GAS, (LP OR NATURAL)
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2. SHEETS
 SHALL SHOW A LISTING FROM AN APPROVED
 TESTING AGENCY.
 F. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 G. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 H. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]