| Date |
Text |
| 2004-01-16 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FLA. ADMIN. CODE |
| | FLA. STATUTES |
| | |
| | 1) SHT 1 OF 4, SPECIFICATION WORKSHEETS |
| | REFERED TO ON THE DEPT. OF BUSINESS REG- |
| | ULATION STAMP, COMMENT #3, SHALL BE SUB- |
| | MITTED WITH PLANS FOR REVIEW. SECTION |
| | 104.2.1. |
| | 2) AN RPZ BACKFLOW IS REQUIRED ON WATER |
| | SERVICE TO SPACE. SECTION 608.13.2. |
| | 3) CONTACT RODNEY COMPO, ENVIRONMENTAL |
| | COMPLIANCE FOR SIZING OF GREASE INTER- |
| | CEPTOR. WASTE ORD. #2938-96. (561) 837- |
| | 4074. |
| | 4) SHT 3 OF 4 FLOOR SINKS ARE REQUIRED |
| | FOR ITEMS 9 & 10, (3 COMP. SINK & SLOP |
| | SINK). HUB DRAINS ARE APPROVED FOR |
| | CLEAR WATER WASTE ONLY. SECTION 802.3 |
| | 5) SHT 3 OF 4 GREASE RISER DIAGRAM, A |
| | VENT IS REQUIRED FOR THE MOP SINK, SECT- |
| | ION 901.2.1 |
| | 6) FIRM LICENSE NUMBER REQUIRED PER FAC |
| | 61G1-16.004(2) & FS 481. |
| | 7) FOLLOWING INFORMATION REQUIRED FOR |
| | GAS PERMIT APPLICATION. |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | B. TYPE OF GAS, (LP OR NATURAL) |
| | C. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | D. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2. SHEETS |
| | SHALL SHOW A LISTING FROM AN APPROVED |
| | TESTING AGENCY. |
| | F. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | G. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | H. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |