| 2004-01-08 00:00:00 | DENIED: | | | PLEASE CLARIFY THAT THE MECHANICAL | | | CONTRACTOR SIGNED ON THE PERMIT | | | APPLICATION WILL BE DOING THE HVAC, | | | GREASE HOOD/GREASE DUCT AND WALK-IN | | | COOLER.SEPARATE PERMITS REQUIRED IF | | | OTHER CONTRACTORS ARE TO PERFORM WORK. | | | SEPARATE PERMIT REQUIRED FOR | | | SUPPRESSION, PLEASE PROVIDE PLANS WITH | | | PERMIT APPLICATION. | | | | | | HVAC: | | | 1.PLEASE PROVIDE OUTSIDE AIR | | | CALCULATIONS PER 2001 FBC(M) 403.3. | | | | | | 2.NOTE ON PLAN SHEET 2 OF 4 REFERS TO | | | SHEET 4 FOR AS-BUILT DRAWING.SHEET 4 | | | INDICATES GREASE DUCT. | | | | | | HOOD/GREASE DUCT: | | | 1.PLEASE INDICATE TERMINATION OF | | | GREASE DUCT IN RELATION TO THE PROPERTY | | | LINES, AND ADJACENT OR CONTINGUOUS | | | BUILDINGS. | | | | | | 2.EXHAUST FAN TO BE HINGED UPBLAST | | | TYPE PER NFPA 96 4-8.2.1 (E). | | | | | | 3.INDICATE SIZE OF GREASE DUCT ON | | | PLAN. | | | | | | 4.SUBMITTAL REQUIRED FOR THE FIRE | | | WRAP IF USED FOR CLEARANCE REDUCTION. | | | | | | WALK-IN COOLER: | | | PROVIDE MANUFACUTER SUBMITTAL DATA WITH | | | PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|