Plan Review Notes
Plan Review Notes For Permit 03120255
Permit Number 03120255
Review Stop M
Sequence Number 1
Notes
Date Text
2004-01-08 00:00:00DENIED:
 PLEASE CLARIFY THAT THE MECHANICAL
 CONTRACTOR SIGNED ON THE PERMIT
 APPLICATION WILL BE DOING THE HVAC,
 GREASE HOOD/GREASE DUCT AND WALK-IN
 COOLER.SEPARATE PERMITS REQUIRED IF
 OTHER CONTRACTORS ARE TO PERFORM WORK.
 SEPARATE PERMIT REQUIRED FOR
 SUPPRESSION, PLEASE PROVIDE PLANS WITH
 PERMIT APPLICATION.
  
 HVAC:
 1.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS PER 2001 FBC(M) 403.3.
  
 2.NOTE ON PLAN SHEET 2 OF 4 REFERS TO
 SHEET 4 FOR AS-BUILT DRAWING.SHEET 4
 INDICATES GREASE DUCT.
  
 HOOD/GREASE DUCT:
 1.PLEASE INDICATE TERMINATION OF
 GREASE DUCT IN RELATION TO THE PROPERTY
 LINES, AND ADJACENT OR CONTINGUOUS
 BUILDINGS.
  
 2.EXHAUST FAN TO BE HINGED UPBLAST
 TYPE PER NFPA 96 4-8.2.1 (E).
  
 3.INDICATE SIZE OF GREASE DUCT ON
 PLAN.
  
 4.SUBMITTAL REQUIRED FOR THE FIRE
 WRAP IF USED FOR CLEARANCE REDUCTION.
  
 WALK-IN COOLER:
 PROVIDE MANUFACUTER SUBMITTAL DATA WITH
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.