Plan Review Notes
Plan Review Notes For Permit 03120255
Permit Number 03120255
Review Stop E
Sequence Number 1
Notes
Date Text
2004-01-07 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE PROVIDE ALL LICENSE #`S
 ON TITLE BLOCK FOR FIRM. PER FAC 61G1-
 16.004. PER FS 481
  
 2)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH A PANEL SCHED-
 -ULE. IF SOME ARE EXISTING, PLEASE LABEL
 AS "E" IF NEW ,,,,,
 PLEASE SHOW WITH OCP/AWG ON PANEL SCHED-
 -ULE.
  
 3)NOTE: PLEASE SEE 700.12E FOR EM/EXT
 LTS. PLEASE SEE FIRE REVIEW COMMENTS.
  
 4)NOTE: PLEASE SEE EQUIPMENT SCHEDULE,
 SHOWS "MR WINTER" WALK-IN COOLER AS 220V
 , ELECTRICAL SERVICE IS SHOWN AS 208V,
 PLEASE VERFIY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]