| 2004-01-07 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: PLEASE PROVIDE ALL LICENSE #`S | | | ON TITLE BLOCK FOR FIRM. PER FAC 61G1- | | | 16.004. PER FS 481 | | | | | | 2)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH A PANEL SCHED- | | | -ULE. IF SOME ARE EXISTING, PLEASE LABEL | | | AS "E" IF NEW ,,,,, | | | PLEASE SHOW WITH OCP/AWG ON PANEL SCHED- | | | -ULE. | | | | | | 3)NOTE: PLEASE SEE 700.12E FOR EM/EXT | | | LTS. PLEASE SEE FIRE REVIEW COMMENTS. | | | | | | 4)NOTE: PLEASE SEE EQUIPMENT SCHEDULE, | | | SHOWS "MR WINTER" WALK-IN COOLER AS 220V | | | , ELECTRICAL SERVICE IS SHOWN AS 208V, | | | PLEASE VERFIY. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|