| Plan Review Notes For Permit 03120255 |
| Permit Number |
03120255 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-15 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 03120255 | | | ADD: 4065 N HAVERHILL | | | CONT: QUALITY MAINENCE | | | TEL: (321)432-5666 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | BUILDING | | | 1SR REVIEW | | | | | | ACTION: DENIED | | | | | | 1) COMMENT# 2 FROM FIRE DEPARTMENT TO BE | | | VARIFIED. FIRE SPRINKLERED BUILDINGS | | | THAT CONTAIN WALK IN COOLERS ALSO RE- | | | QUIRE FIRE SPRINKLERS. | | | 2603.5.1.2(4) WHERE THE COOLER OR | | | FREEZER IS WITHIN A BUILDING, BOTH THE | | | COOLER AND FREEZER AND PART OF THE BUILD | | | ING IN WHICH IT IS LOCATED SHALL BE | | | SPRINKLERED. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|