2004-01-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03120255
 ADD: 4065 N HAVERHILL
 CONT: QUALITY MAINENCE
 TEL: (321)432-5666
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 BUILDING
 1SR REVIEW
  
 ACTION: DENIED
  
 1) COMMENT# 2 FROM FIRE DEPARTMENT TO BE
 VARIFIED. FIRE SPRINKLERED BUILDINGS
 THAT CONTAIN WALK IN COOLERS ALSO RE-
 QUIRE FIRE SPRINKLERS.
 2603.5.1.2(4) WHERE THE COOLER OR
 FREEZER IS WITHIN A BUILDING, BOTH THE
 COOLER AND FREEZER AND PART OF THE BUILD
 ING IN WHICH IT IS LOCATED SHALL BE
 SPRINKLERED.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026