| 2003-12-18 00:00:00 | 1) NOTE # 29 ON TITLE PAGE IS INCORRECT. |
| | STANDPIPES ARE REQUIRED TO BE ERECTED |
| | AFTER CONSTRUCTION HAS PROGRESSED ABOVE |
| | 30 FEET. PLEASE REVISE PLANS AS |
| | NECESSARY. |
| | |
| | 2) THE ENTIRE BUILDING IS REQUIRED TO |
| | BE COMPLETELY FIRE SPRINKLER PROTECTED. |
| | THIS INCLUDES ALL MECHANICAL, |
| | ELECTRICAL, AND TELEPHONE ROOMS. THE |
| | TOP OF ALL STAIRS AND OTHER SHAFTS ARE |
| | ALSO REQUIRED TO BE FIRE SPRINKLER |
| | PROTECTED. |
| | |
| | 3) ALL VOID OR DEAD SPACES SHALL BE FIRE |
| | SPRINKLER PROTECTED UNLESS WRITTEN |
| | VERIFICATION IS RECEIVED THAT THERE WILL |
| | BE NO ACCESS AND NO STORAGE PRESENT |
| | IN THESE AREAS. |
| | |
| | 4) NO FIRE SPRINKLER PROTECTION SHOWN |
| | FOR FIRE PUMP ROOM OR STORAGE ROOM |
| | ON FP-2. |
| | |
| | 5) SINCE THE BUILDING IS A HIGH-RISE |
| | TWO FIRE DEPARTMENT CONNECTIONS WILL |
| | BE REQUIRED. AT LEAST ONE OF THESE |
| | CONNECTIONS SHALL BE LOCATED WITHIN |
| | 150 FEET OF A FIRE HYDRANT. |
| | |
| | 6) NO FIRE SPRINKLER PROTECTION IN |
| | ELEVATOR MACHINE ROOM # 5 ON PAGE FP-2. |
| | |
| | 7) NO FIRE SPRINKLER PROTECTION NOTED |
| | IN SMALL ROOM WITH DOUBLE DOORS |
| | LOCATED IN STORAGE ROOM ON PAGE FP-3. |
| | |
| | 8) NO FIRE SPRINKLER PROTECTION SHOWN |
| | IN SEVERAL METER ROOMS. |
| | |
| | 9) NO FIRE SPRINKLER PROTECTION SHOWN |
| | IN ELEVATOR VESTIBULE 3 & 4 ON PAGE |
| | FP-11, FLOORS 11-16, TOWER. |
| | |
| | 10) PLEASE DOCUMENT ON PLANS THE CODE |
| | SECTION THAT ALLOWS FOR THE DELETION |
| | OF AUTOMATIC FIRE SPRINKLER PROTECTION |
| | FROM RESIDENTIAL BATHROOMS AND CLOSETS. |
| | |
| | 11) THERE APPEARS TO BE NO FIRE |
| | SPRINKLER IN RESIDENTIAL BATHROOMS |
| | AND CLOSETS. PLEASE DOCUMENT REASON |
| | ON PLANS. |
| | |
| | 12) THERE APPEARS TO BE NO FIRE |
| | SPRINKLER PROTECTION IN STORAGE ROOM |
| | FP-11. |
| | |
| | 13) SEVERAL A/C AND WH AREAS ARE NOT |
| | PROTECTED ON PAGE FP-10. |
| | |
| | 14) PLEASE SHOW A TYPICAL ELEVATION |
| | DETAIL OF A TYPICAL TRASH CHUTE FIRE |
| | SPRINKLER ARRANGEMENT. |
| | |
| | 15) PLEASE CLEARLY ILLUSTRATE STANDPIPE |
| | SYSTEMS. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |