| 2004-01-03 00:00:00 | *****PROVISO****** |
| | |
| | SUBMIT REVISIONS BEFORE FRAMING |
| | INSPECTION. |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 |
| | |
| | 1.)THE GIRDER/WALL CONNECTION (SHEET |
| | 3) SPECIFIES HUGHES CONNECTORS; HUGHES |
| | IS NO LONGER IN BUSINESS. |
| | |
| | 2.)THE WOOD CONSTRUCTION NOTES, ITEM |
| | #4, REFERS TO FBC3218.17.NOT IN THE |
| | FBC CODE BOOK. |
| | |
| | 3.)HHGT1 AND HHGT2, CONNECTOR KST260 |
| | SHEET RF1, NAILING CONFLICTS WITH THE |
| | CATALOG AND DESIGN UPLIFT ON THE PLAN |
| | EXCEEDS MAX ALLOWED BY THE CATALOG |
| | (USE THE GREY BAR WITHOUT STRESS |
| | INCREASE FOR STEEL, USP 2003 CATALOG). |
| | |
| | 4.)WOOD-TO-WOOD CONNECTORS ARE |
| | SPECIFIED IN WOOD-TO-MASONRY |
| | APPLICATIONS; FOR EXAMPLE, USP HTW. |
| | ADDRESS. (SHEET RF1). |
| | |
| | 5.)PROVIDE A FIREBLOCK DETAIL FOR THE |
| | DROPPED CEILINGS/SOFFITS, FBC705.3, |
| | 2305.1.4. |
| | |
| | 6.)PROVIDE STATEWIDE OR SITE SPECIFIC |
| | PRODUCT APPROVALS FOR |
| | GARAGE DOOR |
| | GLASS BLOCK |
| | FIXED GLASS WINDOW |
| | |
| | 7.)PROVIDE CORRECT PRODUCT APPROVAL |
| | AND STATEWIDE PRODUCT APPROVAL FOR THE |
| | SHUTTERS.SAFEGUARD IS OUT OF BUSINESS. |
| | |
| | 8.)REMOVE THE TITLE BLOCK FOR AFFINITI |
| | FROM THE PLAN AS THEY ARE NOT THE |
| | DESIGNER OF RECORD. |
| | |
| | 9.)THE ENGINEER'S NAME AND LICENSE |
| | NUMBER IS TO BE PRINTED ON THE PLAN, |
| | FAC61G15-23.002. |