| Date |
Text |
| 2004-04-15 00:00:00 | DENIED |
| | |
| | 1)THE ENGINEER'S TITLE BLOCK INFORMATION |
| | IS ILLEGIBLE ON SOME SHEETS OF THE |
| | PLANS, WHERE STAMPED ON TOP OF OTHER |
| | INFORMATION. PLEASE CORRECT. |
| | |
| | 2) FBC SECTION 2319.17 REFERENCED UNDER |
| | WOOD CONSTRUCTION NOTES ON SHEET 7 ONLY |
| | APPLIES IN THE HIGH VELOCITY HURRICANE |
| | ZONE. THIS DOES NOT APPLY IN THE CITY OF |
| | WPB WHICH IS NOT LOCATED IN THE HVHZ. |
| | PLEASE REMOVE THIS FROM THE PLAN. |
| | |
| | 3) THE USP TA16 CONNECTOR REQUIRES (9) |
| | 10D NAILS FOR 1205# OF UPLIFT. CORRECT |
| | THIS ON THE ANCHOR SCHEDULE ON RF-1. |
| | |
| | 4) THE TRUSS ANCHOR SCHEDULES ON RF-1 |
| | AND SD2 CONTAIN CONFLICTING INFORMATION. |
| | THE UPLIFT VALUES ARE DIFFERENT FOR THE |
| | SAME ID TAGS. PLEASE REMOVE ONE OF THEM |
| | FROM THE PLANS. |
| | |
| | 5) SUBMIT STATE OR LOCAL PRODUCT |
| | APPROVAL FOR THE WEATHERGUARD STORM |
| | PANELS. SPECIFY THE CONNECTION TYPE AND |
| | FASTENERS THAT WILL BE USED BY CIRCLING |
| | OR HIGHLIGHTING THE APPROPRIATE ITEMS ON |
| | THE PRODUCT APPROVALS. |
| | |
| | 6)PLEASE SUBMIT THE FOLLOWING ADDITIONAL |
| | INFORMATION REQUIRED FOR THE ROYAL WALL |
| | SYSTEM. SUBMIT ENGINEERING CALCULATIONS |
| | FOR THE PANELS. SUBMIT A LETTER FROM A |
| | LICENSED THRESHOLD INSPECTOR STATING |
| | THAT AN INSPECTION WILL BE MADE AT THE |
| | MANUFACTURED SITE OF THE JOB SPECIFIC |
| | COMPONENTS TO VERIFY CONSTRUCTION |
| | COMPLIANCE OF THE COMPONENTS WITH THE |
| | ENGINEERED DESIGN. SEE ATTACHED MEMO. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |