1 |
|
| Notes |
| Date |
Text |
| 2003-12-15 00:00:00 | DENIED: | | | 1.PLEASE PROVIDE A COMPLETED FORM 600C | | | OR ENERGY & MANUAL J CALCULATION FOR THE | | | ADDITION ONLY. | | | | | | 2.RETURN AIR NOT IDENTIFIED ON THE | | | BUILDING OR MECHANICAL PLAN.PLEASE | | | INDICATE RETURN AIR GRILLE SIZE OR | | | LOUVERED DOOR ON THE AHU CLOSET. | | | | | | 3.PLEASE NOTE, CONDENSATE SHALL | | | TERMINATE A MINIMUM OF 12" FROM THE | | | BUILDING STRUCTURE. 2001 FBC 1503.4.4. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|