| Plan Review Notes For Permit 03120045 |
| Permit Number |
03120045 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-08 00:00:00 | *********** UNSAT **************** | | | | | | 1)NOTE: PLANS REQUIRE MORE INFORMATION | | | ON WHICH WALLS ARE BEING DEMOLISHED AND | | | WHICH ARE NEW. PLEASE ALSO PROVIDE | | | INFORMATION IF THIS IS GOING TO BE A | | | NEW SPACE OR A REMODEL ETC? | | | | | | 2)NOTE: PLEASE PROVIDE ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH A SUBMITTED | | | PANEL SCHEDULE. | | | | | | 3)NOTE: PLEASE PROVIDE INFORMATION FOR | | | ANY EM/EXT LTS AND CIRCUITING PER 700.12 | | | -E. | | | | | | 4)NOTE: PLEASE CLARIFY NEW OR EXISTING | | | SIGN CIRCUIT PER 600.5 | | | | | | PLEASE SEE COMMENTS FROM OTHER REVIEWERS | | | THAT MAY HAVE AN AFFECT ON ELECTRICAL | | | PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|