Plan Review Notes
Plan Review Notes For Permit 03120045
Permit Number 03120045
Review Stop E
Sequence Number 1
Notes
Date Text
2003-12-08 00:00:00*********** UNSAT ****************
  
 1)NOTE: PLANS REQUIRE MORE INFORMATION
 ON WHICH WALLS ARE BEING DEMOLISHED AND
 WHICH ARE NEW. PLEASE ALSO PROVIDE
 INFORMATION IF THIS IS GOING TO BE A
 NEW SPACE OR A REMODEL ETC?
  
 2)NOTE: PLEASE PROVIDE ALL CIRCUITING ON
 PLANS AND CORRELATE WITH A SUBMITTED
 PANEL SCHEDULE.
  
 3)NOTE: PLEASE PROVIDE INFORMATION FOR
 ANY EM/EXT LTS AND CIRCUITING PER 700.12
 -E.
  
 4)NOTE: PLEASE CLARIFY NEW OR EXISTING
 SIGN CIRCUIT PER 600.5
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 THAT MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  